Remote mounting kits outdoor sensor kit, Specifications, Dimensions – Hydrolevel 3250-Plus User Manual
Page 16
16
83 Water Street • New Haven, CT 06511 • Phone (203) 776-0473 • FAX (203) 773-1019 •
www.hydrolevel.com
REMOTE MOUNTING KITS
OUTDOOR SENSOR KIT
Hydrolevel's optional Outdoor Sensor Kit automatically activates outdoor reset functionality and warm weather shutdown capa-
bility when plugged in to the Fuel Smart HydroStat control. This low cost, easy to install kit is available separately at Hydrolevel
distributors.
Part No.
Description
48-140
Model OS-100 Outdoor Sensor Kit
Part No.
Description
48-101
HydroStat Remote Mount Kit with 24" sensor
48-102
HydroStat Remote Mount Kit with 48" sensor
Part No.
Description
48-103
HydroStat Remote Mount Kit with 10' sensor
48-104
HydroStat Remote Mount Kit with 20' sensor
48-121
HydroStat Pipe Mounting Kit with 48" sensor
SPECIFICATIONS
FUEL SMART HYDROSTAT MODEL 3250-Plus
DIMENSIONS
LIMITED MANUFACTURERʼS WARRANTY
We warrant products manufactured by Hydrolevel Company to be free from defects in
material and workmanship for a period of two years from the date of manufacture or
one year from the date of installation, whichever occurs first. In the event of any claim
under this warranty or otherwise with respect to our products which is made within
such period, we will, at our option, repair or replace such products or refund the pur-
chase price paid to us by you for such products. In no event shall Hydrolevel Company
be liable for any other loss or damage, whether direct, indirect, incidental or conse-
quential. This warranty is your EXCLUSIVE remedy and shall be IN PLACE OF any other
warranty or guarantee, express or implied, including, without limitation, any warranty
of MERCHANTABILITY or fitness for a particular purpose. This warranty may not be
assigned or transferred and any unauthorized transfer or assignment thereof shall be
void and of no force or effect.
Input voltage
120 VAC, 60 HZ
Burner contacts
7.4 FLA, 44.4 LRA@120 VAC
Circulator contacts
5.8 FLA, 34.8 LRA@120 VAC
Operating range – low limit
Off or 110°F (43°C) - 200°F (93°C)
Operating range – high limit
100°F (38°C) - 220°F (104°C)
Operating range – differentials
Automatic
Thermostat heat anticipator setting 0.2A
3250-1113