11

TEMP ACTIVE

Indicates that the Fuel Smart

HydroStat control is powered and that the temperature

function is active.

TEMP HI TEMP

Illuminates when the boiler water

temperature reaches the high limit setting. It will remain lit

until the water temperature falls 10°. The Fuel Smart

HydroStat prevents burner operation while this LED is on.

See Differential explanation on page 7.

LWCO ACTIVE

Indicates that the low water cut-off

(LWCO) function of the Fuel Smart HydroStat is active. When

the control is installed with a Hydrolevel Electro-Well™, this

LED will be on at all times when the control is powered.

IMPORTANT: If the control is installed with a well other than

the Electro-Well™, this LED will not illuminate indicating that

the control is not providing low water cut-off functionality.

LWCO LOW WATER

Indicates that the boiler is in a

low water condition. The HydroStat control will prevent

burner operation during this condition. If the LOW WATER

light is blinking, the control has been programmed to provide

lock-out protection in the event a low water condition is

detected (see Manual Reset Low Water Cut-Off on page 9).

Pressing the TEST/SETTINGS button will reset the control.
IMPORTANT: The system must be checked by a qualified

heating professional prior to resuming operation.

WARNING: ALLOW THE BOILER TO FULLY COOL

BEFORE ADDING WATER.

ECONOMY ACTIVE

Indicates that the Thermal

Targeting function is active and the Fuel Smart HydroStat will

reduce boiler temperature to conserve fuel. The Economy

feature is activated using the ECONOMY dial. (See “How

Thermal Targeting Works” on page 8 for more information).

ECONOMY TARGET

When the Economy feature is

active, the Fuel Smart HydroStat continually sets target

temperatures below the high limit setting to maximize fuel

efficiency. When the boiler water reaches the target

temperature, the LED illuminates and the burner will shut

down. The boiler water will continue to circulate and heat the

house as long as the thermostat call continues. The LED will

stay lit until the boiler temperature drops below the

differential set point at which point the boiler will be allowed

to fire again. See Differential explanation on page 7.

NOTE: This LED illuminates regularly during normal boiler

operation.

TEST/SETTINGS Button

To Test Low Water Cut-Off: Press and hold the Test/

Settings button for 5 seconds. The display will read LCO.

LWCO TEST

00

The red Low Water light should illuminate and the burner

circuit (B1 and B2) should de-energize. NOTE: The control

must be installed with a Hydrolevel Electro-Well™ for low

water cut-off functionality (see page 2 for more details).
To View Current Settings: Press and release the

Test/Settings Button in short intervals to sequentially display

the following settings:

HIGH LIMIT SETTING

00

̄

LOW LIMIT SETTING

00

̄

ECONOMY SETTING

000

̄

CURRENT TARGET TEMPERATURE

The display will return to boiler temperature (default) if

Test/Settings Button in not pressed for 5 seconds.

LED LEGEND and TEST/SETTINGS BUTTON