beautypg.com

Hydrolevel VXT-120 V2 User Manual

Page 3

background image

30-Second

2-Minute

(Factory Setting)

4-Minute

6-Minute

8-Minute

10-Minute

The feed delay feature is designed to prevent boiler flooding by allowing time for condensate to return to the boiler prior to

feeding. If the returns and vents are in good condition, the 2-minute factory setting is usually sufficient. If for any reason con-

densate takes longer to return to the boiler (such as old return lines or long horizontal runs), a longer delay setting should be

selected.

NOTE: SELECT ONLY ONE DIPSWITCH CORRESPONDING TO THE DESIRED FEED DELAY.

LWCO

(Factory Setting)

1-Gallon

2-Gallon

3-Gallon

4-Gallon

5-Gallon

LWCO Setting: The VXT feeder is shipped in the LWCO feed setting. When operating in this setting, the VXT will feed only

until the low water cut-off re-energizes the burner circuit (or a maximum of 5 gallons). This will restore boiler operation, but on

some applications may only be enough water to satisfy the

minimum requirements. If additional water is needed to reach the

boilerʼs

normal operating level, the 1-Gallon to 5-Gallon settings should be selected using the instructions below.

DO NOT USE LWCO SETTING WITH SAFGARD MODEL OEM-170TD.

1 Gallon to 5 Gallon Settings: When the 1 to 5 Gallon settings are used, the feeder will continue to feed until the cycle is

complete, regardless of when the low water cut-off is satisfied. These settings should be used only when the LWCO setting

does not provide adequate water to restore the boiler to a

normal operating level. Use the following instructions when choosing

these settings:
Boilers with probe-type cut-offs:
1. With power to the system on and the thermostat off, lower

the water level to approximately 1/2" below the probe.

2. Press the FEED button on the water feeder and, using a

watch with a second hand, time how long it takes boiler

water to reach the

normal operating level (Usually the

middle of the gauge glass unless otherwise specified by

the boiler manufacturer).

3. Round the time to the nearest minute and set the feeder

for the corresponding number of gallons.
Example: If it takes 1 minute and 15 seconds for water to

rise from 1/2" below the probe to the normal operating

level, round to 1 minute and set the feeder for 1-Gallon.

4. Once the Feed Amount has been set, perform a test cycle

by lowering the water a second time (following proce-

dures in Step 1 above) and allowing the feeder to replen-

ish the water automatically.

Boilers with float-type cut-offs:
1. With power to the system on and the thermostat off, lower

the water level until 1/4" is visible in the gauge glass.

2. Press the FEED button on the water feeder and, using a

watch with a second hand, time how long it takes boiler

water to reach the

normal operating level (Usually the

middle of the gauge glass unless otherwise specified by

the boiler manufacturer).

3. Round the time to the nearest minute and set the feeder

for the corresponding number of gallons.
Example: If it takes 2 minutes and 10 seconds for

water to rise from 1/4" in the gauge glass to the normal

operating level, round to 2 minutes and set the feeder for

2-Gallons.

4. Once the Feed Amount has been set, perform a test cycle

by lowering the water a second time (following proce-

dures in Step 1 above) and allowing the feeder to replen-

ish the water automatically.

NOTE: SELECT ONLY ONE DIPSWITCH CORRESPONDING TO THE DESIRED FEED AMOUNT.

CAUTION: BOILER FLOODING CAN OCCUR IF THE FEEDER IS NOT SET PROPERLY.

UNLIKE OTHER FEEDERS, THE 1-GALLON TO 5-GALLON SETTINGS WILL FEED THE FULL

CYCLE REGARDLESS OF WHEN THE WATER REACHES THE LOW WATER CUT-OFF.

Step 4

Set the Feed Delay

Step 5

Set the Feed Amount

Step 6

Attach Service Tag

Complete the information at the top of the service tag provided and attach tag near the VXT Water Feeder.