Connect input voltage (120 VAC, 60 HZ) to

terminals 1 and 2.

Connect terminal 2 to burner circuit neutral.

Connect terminal P2 to burner Circuit in

series with other limit controls. Consult boil-

er manufacturer instructions for proper ter-

minal connections. Control should be wired

in series with and before other limit controls.

Optional water feeder connection.

Connect feeder N to terminal 2. Connect Feeder

H to terminal 1. Connect feeder “FEED” or “W”

to terminal A. For water feeders with 2 leads,

connect feeder neutral to terminal 2 and feeder

hot to terminal A.

NOTE: Use of a solenoid valve or McDonnell &

Miller Model 101A water feeder may cause

flooding and is not recommended for use with

this low water cut-off.

OPTIONAL ACTIVATION

Connect “SMTCYC” terminal on the

CycleGard control to the orange burner wire

(120VAC) located under the primary. See

detail illustration at the right.

See SmartCycle description on next page.

1

2

3

4

Detail of SmartCycle Connection

Model CG470

2

WIRING – Model CG470