5 operating interface, 6 indicators, Addressing jack (addr) indicators display meaning – EUCHNER AS-i Safety Output Relay with four standard inputs User Manual
Page 15: As-i safety output relay with four standard inputs
AS-i Safety Output Relay with four standard inputs
Product Description
Subject to reasonable modifications due to technical advances
Id.-No.: 103573
Issue date - 28.5.2009
EUCHNER GmbH + Co. KG
15
Kohlhammerstraße 16 • D-70771 Leinfelden-Echterdingen
Tel. +49/711/75 97-0 • Fax. +49/711/753316
4.5
Operating interface
4.6
Indicators
Switch to select the operational mode:
PRG
Safety relevant AS-i address can be programmed
Secure operation not possible.
RUN
Secure operation possible, non-safety relevant AS-i address can be
programmed.
Addressing jack (ADDR)
Indicators
Display
Meaning
PWR
off
No supply power
green 1 Hz flashing
Operational power on, safety relevant AS-i address and/or
AS-i AB address is “0”
green (on)
Supply power on
Fault
off
AS-i communication OK
red (on)
No data exchange with the AB slave
Out
off
Output Relay switched off
green 1 Hz flashing
Error lock state, waiting for start signal, after transmission
of start signal Output Relay switches on
green 8 Hz flashing
The device is in an un-lockable error state. The device
resumes regular operation after the Monitor sent the sig-
nal “error unlock”.
green (on)
Output Relay switched on
Alarm
off
AS-i output bit A0 not set
red (on)
AS-i output bit A0 set
I1, I2, I3, 1.Y1 off
Corresponding input is not on
yellow
cyclic flashing
Switch set to PRG
yellow (on)
Corresponding input is on
I
1
I
3 1.Y1
I
2
I
–
I
1
1.13
ASI
+
I
+
I
2
1.14
ASI
–
I
+
I
3
1.23
NC
I
+
1.Y1
1.24
NC
ADDR
RUN
PRG
FAULT
ALARM
PWR
OUT