5 operating interface, 6 indicators, Addressing jack (addr) indicators display meaning – EUCHNER AS-i Safety Output Relay with four standard inputs User Manual

Page 15: As-i safety output relay with four standard inputs

background image

AS-i Safety Output Relay with four standard inputs

Product Description

Subject to reasonable modifications due to technical advances

Id.-No.: 103573

Issue date - 28.5.2009

EUCHNER GmbH + Co. KG

15

Kohlhammerstraße 16 • D-70771 Leinfelden-Echterdingen

Tel. +49/711/75 97-0 • Fax. +49/711/753316

4.5

Operating interface

4.6

Indicators

Switch to select the operational mode:

PRG

Safety relevant AS-i address can be programmed
Secure operation not possible.

RUN

Secure operation possible, non-safety relevant AS-i address can be
programmed.

Addressing jack (ADDR)

Indicators

Display

Meaning

PWR

off

No supply power

green 1 Hz flashing

Operational power on, safety relevant AS-i address and/or
AS-i AB address is “0”

green (on)

Supply power on

Fault

off

AS-i communication OK

red (on)

No data exchange with the AB slave

Out

off

Output Relay switched off

green 1 Hz flashing

Error lock state, waiting for start signal, after transmission
of start signal Output Relay switches on

green 8 Hz flashing

The device is in an un-lockable error state. The device
resumes regular operation after the Monitor sent the sig-
nal “error unlock”.

green (on)

Output Relay switched on

Alarm

off

AS-i output bit A0 not set

red (on)

AS-i output bit A0 set

I1, I2, I3, 1.Y1 off

Corresponding input is not on

yellow
cyclic flashing

Switch set to PRG

yellow (on)

Corresponding input is on

I

1

I

3 1.Y1

I

2

I

I

1

1.13

ASI

+

I

+

I

2

1.14

ASI

I

+

I

3

1.23

NC

I

+

1.Y1

1.24

NC

ADDR

RUN

PRG

FAULT

ALARM

PWR

OUT