Operating instructions safety system ces-ap-c.2-ah, Setup, Led indicators – EUCHNER CES-AP-CL2-AH (Unicode) User Manual
Page 15: Teach-in function for actuator
Operating Instructions Safety System CES-AP-C.2-AH
15
Setup
LED indicators
LED
Color
State
Significance
STATE
green
illumi-
nated
Normal operation: Door closed
flashing
- Door open
- Actuator in boundary area(refer to the status table for
further signal functions)
DIA
red
illumi-
nated
- Internal electronics fault
- Fault at the inputs/outputs
Teach-in function for actuator
The actuator must be allocated to the safety switch using a teach-in function before
the system forms a functional unit.
During a teach-in operation, the safety outputs and the monitoring output OUT are
in a high-resistance state, i.e. the system is in the safe state.
Important:
Ì
The safety switch disables the code of the previous actuator if teach-in is
carried out for a new actuator. Teach-in is not possible again immediately for
this actuator if a new teach-in operation is carried out. The disabled code is
deleted again in the safety switch only after a third code has been taught.
Ì
The safety switch can only be operated with the last actuator taught.
Ì
If the switch detects an actuator which has already been taught when in
teach-in standby state, this state is ended immediately and the switch chang-
es to normal state.
Ì
The actuator being taught is not activated if it is within the operating dis-
tance for less than 60 s.
Actuator teach-in
1. Apply operating voltage to the safety switch.
¨
A self-test is performed for approx. 0.5 s. After this, the LED flashes cycli-
cally three times and signals that it is in standby state for teach-in.
Standby state for teach-in remains active for approx. 3 minutes.
2. Move new actuator to the read head.
¨
Teach-in operation starts, green LED flashes (approx. 1 Hz). During teach-in, the
safety switch checks whether the actuator is a disabled actuator. Provided this
is not the case, the teach-in operation is completed after approx. 60 seconds,
and the green LED goes out. The new code has now been stored, and the old
code is disabled.
3. To activate the new actuator code from the teach-in operation in the safety
switch, the operating voltage to the safety switch must then be switched off
for min. 3 seconds.