Technical data – EUCHNER CES-A-AEA-04B (Unicode) User Manual
Page 23

Operating Instructions Safety System CES-A-AEA-02B/CES-A-AEA-04B
23
Technical Data
Parameter
Value
Unit
min.
typ.
max.
Housing material
Plastic PA6.6
Dimensions
114 x 99 x 45
mm
Weight
0.25
kg
Ambient temperature at U
B
= DC 24 V
-20
-
+55
°C
Atmospheric humidity, not condensing
-
-
80
%
Degree of protection
IP20
Degree of contamination
2
Installation
DIN rail 35 mm according to EN 60715
Number of read heads
Max. 4 read heads per evaluation unit
Connection (screw terminals)
0.14
-
2.5
mm²
Operating voltage U
B
(regulated, residual ripple < 5 %)
21
24
27
V DC
For the approval according to
the following applies
Operation only with UL Class 2 power supply, or equivalent measures
Current consumption I
B
(with relay energized)
1)
-
220
270
mA
External fuse (operating voltage U
B
)
0.4
-
8
A
Safety contacts
2 (relays with internally monitored contacts)
Switching current (relay outputs)
mA
- At switching voltage AC/DC
1 ... 60 V
1
2)
-
300
- At switching voltage AC/DC
17 ... 30 V
15
-
6000
- At switching voltage AC
17 ... 230 V
15
-
1500
Switching load according to
Max. AC 30 V, class 2 / max. DC 60 V, class 2
External fuse (safety circuit) according to EN 60269-1
6 A gG or 6 A circuit breaker (characteristic B or C)
Utilization category to EN 60947-5-1
AC-12 60V 300mA 50Hz / DC-12 60V 300mA
AC-12 30V 6A / DC-12 30V 6A
AC-15,230V 1.5A 50Hz / DC-13 24V 1.2A
Classification according to EN 60947-5-3
PDF-M
Rated insulation voltage U
i
250
V
Rated impulse withstand voltage U
imp
4
kV
Rated conditional short-circuit current
100
A
Resilience to vibration
According to EN 60947-5-2
Mechanical operating cycles (relays)
10 x 10
6
Switching delay from state change
3)
- 4 activated actuators
-
-
450
ms
- 3 activated actuators
-
-
370
- 2 activated actuators
-
-
290
- 1 activated actuator
-
-
210
Time difference between the switching points of the two
relays (with 4 activated actuators)
-
-
400
ms
Manual start operating mode
- Duration of operation of start button
250
-
-
ms
- Start button response delay
-
200
300
Current via feedback loop Y1/Y2
5
8
10
mA
Permissible resistance via feedback loop
-
-
600
Ω
Ready delay
4)
-
10
12
s
Dwell time
5)
3
-
-
s
Switching frequency max.
6)
-
-
0.25
Hz
Monitoring outputs (diagnostics DIA, release 01...02, semi-
conductor output, p-switching, short circuit-protected)
- Output voltage
0.8 x U
B
-
U
B
V DC
- Max. load
-
-
20
mA
Start button input S, test input TST
- Input voltage LOW
0
-
2
V DC
HIGH
15
-
U
B
- Input current
HIGH
5
8
10
mA
EMC protection requirements
In acc. with EN 60947-5-3
Reliability values according to EN ISO 13849-1
Switching current at 24 V DC
≤ 0.1 A
≤ 1 A
≤ 3 A
Category
4
PL
e
PFH
d
1.3 x 10
-8
1.5 x 10
-8
Mission time
20
years
Number of switching cycles/year
506 000
100 000
23 000
1) Without taking into account the load currents on the monitoring outputs.
2) If a switching current > 300 mA in conjunction with a switching voltage > 15 V or an inductive or capacitive load is switched once using the relay outputs, it is no longer possible to reliably
switch small currents (< 15 mA) due to the contact erosion on the gold contacts.
3) Corresponds to the risk time according to EN 60947-5-3. This is the maximum switch-off delay for the safety outputs following removal of the actuator. In case of EMC interference in excess of
the requirements in accordance with EN 60947-5-3, the switch-off delay can increase to max. 750 ms. After a brief actuation < 0.8 s, the switch-on delay can increase to max. 3 s if this is fol-
lowed immediately by further actuation.
4) After the operating voltage is switched on, the relay outputs are switched off and the monitoring outputs are set LOW during the ready delay. For the visual indication of the delay, the green
STATE LED flashes at a frequency of approx. 15 Hz.
5) The dwell time is the time that the actuator must be inside or outside the operating distance.
6) In case of monitoring with feedback loop, the actuators must remain outside the operating distance, e.g. with a door open, until the feedback circuit is closed.