Wire requirements and specification, Terminate wiring, Interface series – ETC Unison Heritage Rackmount Contact Interface User Manual
Page 2: N o t e
E T C I n s t a l l a t i o n G u i d e
Interface Series
Unison
®
Heritage Rack Mount Contact Interface
Page 2 of 3
Electronic Theatre Controls, Inc.
Wire Requirements and Specification
Terminate Wiring
Step 1:
Terminate LinkPower.
a: Strip 7/16” (11mm) from the ends of each LinkPower wire (typically black and white
twisted pair).
b: Using a jewelers screwdriver, open the ULP+ and ULP- terminals.
c: Insert the (typically white) wire from the pair into the ULP+ terminal.
d: Insert the (typically black) wire from the pair into the ULP- terminal.
e: Tighten each terminal screw firmly to secure the wires in place.
Step 2:
Terminate Auxiliary power (24 Vdc) wiring.
a: Strip 7/16” (11mm) from the ends of each Auxiliary power wire (typically a 16 AWG
black and red twisted pair).
b: Using a jewelers screwdriver, open the +24 VDC and Common terminals.
c: Insert the (typically red) wire from the pair into the+ 24 VDC terminal.
d: Insert the (typically black) wire from the pair into the Common terminal.
e: Tighten the terminal screw to secure the wire(s) in place.
Purpose
Wire Type
Notes
Link Power
(LinkConnect)
control network
Belden 8471
(or approved equal)
Echelon
®
LinkPower
®
(LinkConnect) control net-
work utilizes low voltage Class II wire.
Wiring is topology free, polarity independent with a
maximum total system length of 1,640 feet (500m).
Auxiliary power
(24 Vdc)
(2) 18 -10 AWG
(0.75 - 6mm
2
)
Chassis Ground
18 - 10 AWG
(0.75-6mm
2
)
Required when wiring is not installed in grounded
metal conduit.
Contact Input and
Contact Output
terminals
24 - 12 AWG
(0.2 - 2.5mm
2
)
Two wires are required per switch (switch in or
switch out and common). Supports up to 1,000 feet
(305m) of 16 AWG (1.5mm
2
) between input and
common.
N o t e :
LinkPower is topology free and polarity independent. You can install your LinkPower
wiring in any combination of bus, star, loop, or home-run. If more than one pair of
LinkPower wires are to be terminated be sure to label each pair individually. Each ULP
terminal can accept up to two conductors per terminal.