E T C I n s t a l l a t i o n G u i d e
Light Sensor
Unison Paradigm Light Sensor Installation Guide
Page 8 of 8
Electronic Theatre Controls, Inc.
Binding Sensors to Paradigm
The Paradigm Architectural Control Processor (P-ACP) to which this sensor is
physically wired to must learn, or be told, the station hardware address (known as a
neuron ID). When the sensor is unbound from the connected P-ACP, the service pin
LED blinks.
The neuron ID is labeled on the sensor control board and can be manually entered
into the configuration using LightDesigner software. Alternatively, the sensor can be
identified using the service pin button (designated with “S” on the button) and by the
connected Paradigm ACP using its [LonWorks Connections] menu. Reference the
related source documentation, either the LightDesigner Online Help System or the
Unison Paradigm Architectural Control Processor Configuration Manual; specifically
the section on Arch Setup Menu, LonWorks Connections.
Record a Target Lighting Value
The Paradigm Light Sensor includes a button that by default provides recording of
target lighting values for its dimming daylight harvesting feature. Pressing the record
button enables a five second timer and illuminates the LED red. When the timer
expires, the measured light level is stored as the amount of desired light that the
connected Paradigm control system should maintain, and the red LED blinks twice to
confirm.