Soft ceiling tile installation, Light sensor – ETC Unison Paradigm Light Sensor User Manual
Page 5
E T C I n s t a l l a t i o n G u i d e
Light Sensor
Unison Paradigm Light Sensor Installation Guide
Page 5 of 8
Electronic Theatre Controls, Inc.
Soft Ceiling Tile Installation
Step 1:Pull the Belden 8471 (or equivalent) and 14 AWG (2.5mm
2
) ground wire to the
installation location.
Step 2:Orient the smooth side of the mounting plate to the ceiling tile and insert the
soft ceiling tile adaptor through the two small holes near the center of the
mounting plate.
Step 3:Poke the tines through the ceiling tile, then bend each tine over in opposite
directions for a secure fit.
Step 4:If you are installing the sensor in series with other sensors or stations
(continuing the data run), use the provided LinkConnect pigtail, ESD ground
pigtail and WAGO connectors to make the terminations. If you are not
continuing the data run, proceed to step 5.
Step 5:If you are installing the primary and/or optional second light sensor
remotely from the controller, reference
"Installing the Light Sensors Remotely
on page 6, then return to these instructions. If you are not remoting
a light sensor, proceed to step 6.
poke the adapter through the ceiling tile, then bend
it over for a secure fit.
LinkConnect pigtail and
WAGO connectors
(optional use)
terminate
wires here
optional
sensor wires
install
ed control
wire
installed control wire to next stati
on
sensor pigtail
a: Strip 3/16” (5mm) of insulation from each installed wire.
b: Open the three terminal levers on a WAGO connector and
insert the installed (typically black) Belden 8471
LinkConnect wire, the black lead from the sensor pigtail,
and the continuing Belden 8471 (typically black) wire into
the terminals.
c: Close the levers onto the wires.
d: Repeat the above for the installed (typically white) Belden
8471 LinkConnect wire and the remaining pigtail from the
sensor, as well as the ESD ground wires using a new
WAGO connector for each termination type.