Iii. c – Elkhart Brass SPIT-FIRE 8394053 Monitor User Manual
Page 5
5
SM-1000BE-HL Nozzle (flows from 300-GPM @ 60-PSI to 1000-GPM @ 82-PSI)
SM-1250BE-HL Nozzle (rated flow is 1250-GPM @ 86-PSI)
SM-2000BE-HL Nozzle (rated flow is 2000-GPM @ 86-PSI)
(See Nozzle flow graphs in section IX on page 23)
C. Control System (Typical System)
1. Motor Control Box:
NEMA #4X Stainless Steel Enclosure. Requires 120-VAC, 60-Hz., Single Phase
power source.
AC power ON / OFF Selector switch. AC Power ON pilot light.
AC/DC Power supply with 24-VDC output for controls.
All control relays to have 24-VDC coil inputs.
37mA relay inputs are for: Monitor (UP, DOWN, LEFT, & RIGHT), Nozzle
(STRAIGHT & FOG) and Water Valve (OPEN & CLOSE).
Conduit knockouts and hubs supplied by customer unless otherwise specified.
Meets (NFPA 70) NEC: 2005, Article 501 - Class I, Groups “B, C, & D,” Division 2 &
Article 505 - Class I, Zone 2, AEx nA IIC T4 requirements.
CE Certified to ATEX 94/9/EC(Group II, Category 3).
2. Control Box:
NEMA #4X (IP-66) controls to operate one thru six monitors includes:
Control power (ON / OFF) switch and pilot light.
Water Valve (OPEN / CLOSE) push button switches and pilot lights, one set per
monitor.
Nozzle (STRAIGHT / FOG) spring return switch.
Monitor (UP / DOWN / LEFT / RIGHT) spring return switch.
Conduit knockouts and hubs supplied by customer unless otherwise specified.
Meets (NFPA 70) NEC: 2008, Article 500 - Class I, Groups “B, C, & D”, Division 2
& Article 505 - Class I, Zone 2, AEx nA IIC T4 requirements.
3. Junction Box:
NEMA #4X (IP-66) water tight, corrosion resistant ATEX certified & UL Listed,
enclosure with terminals, for hazardous locations.
Provided with Stainless Steel, 1½” N.P.T. female Conduit Hub.
Three motor cables with Stainless Steel cord grips mounted in bottom of enclosure
and terminated to terminals inside.
Junction Box is supplied with bracket to be installed at flanged base of monitor, using
two of the eight flange bolts for mounting.
CE Certified to ATEX 94/9/EC( Group II, Category 3).
III. C
ONTROL
S
YSTEM
S
PECIFICATIONS
A. Electrical Requirements:
Nozzle Motor 120 VAC, 60 Hz., 1 Phase, 0.30 - Amps current.
Monitor Motors 120 VAC, 60 Hz., 1 Phase, 0.90 - Amps current per motor.
Control Power 24 VDC, and 37mA current per input (typically 7 for monitor and 1 valve).
Main Power
120 VAC, 60 Hz., 1 Phase, to be terminated at Motor Control Box.
Current to be supplied at Motor Control Box is 6-Amps minimum.