Elkhart Brass Scorpion RF 8394-07 User Manual
Page 16
16
VERTICAL TRAVEL STOP IS FACTORY
SET AT 90 ABOVE TO 45 BELOW
HORIZONTAL
STOP SCREWS ARE FACTORY
INSTALLED AT THESE LOCATIONS.
(180 HORIZONTAL TRAVEL.)
Rotational Limit Settings
8294-06
The rotational stop screws (see Figure 4) set the monitor rotational limits (left-right and up-down)
to satisfy the application requirements, as well as NFPA* requirements. The monitor is shipped
from the factory with the horizontal travel limits set at 90 degrees left and 90 degrees right of
the zero (straight ahead) position. The vertical travel limits are factory set at 90 degrees above,
and 45 degrees below horizontal. If the application requires the rotation limits to be changed,
relocate threaded stop screws to required positions per chart below. Apply Loctite 242 or
equivalent to stop screws and hex head plugs prior to reinstalling (stop screw holes are identified
on the monitor by a stamped letter adjacent to each hole). All empty stop screw holes should be
filled with a hex head plug.
8394-07
The rotational stop screws (see Figure 4) set the monitor rotational limits (left-right and up-down)
to satisfy the application requirements, as well as NFPA* requirements. The monitor is shipped
from the factory with the horizontal travel limits set at 90 degrees left and 90 degrees right of
the zero (straight ahead) position. The vertical travel limits are factory set at 90 degrees above,
and 45 degrees below horizontal. If the application requires the rotation limits to be changed,
relocate threaded stop screws to required positions per chart below. Apply Loctite 242 or
equivalent to stop screws and hex head plugs prior to reinstalling (stop screw holes are identified
on drawing 98031050). All empty stop screw holes should be filled with a hex head plug
8294-06 EXT
Monitor can be rotated 90° left or 90° right of the zero (straight ahead) position. The vertical
travel is either Master Stream (+30 to -135°) or Egress (+0° to -135°). Horizontal travel limits
can NOT be changed.
Monitor can be rotated 90° left or 90° right of straight ahead. Stops are mechanically fixed by a
stop screw and milled slot in base. Stop screw must remain in place in monitor base.
Figure 4: Scorpion RF Rotational Stops
VERTICAL TRAVEL STOP IS FACTORY
SET AT 90 ABOVE TO 45 BELOW
HORIZONTAL
STOP SCREWS ARE FACTORY
INSTALLED AT THESE LOCATIONS.
(180 HORIZONTAL TRAVEL.)