Installation Step 4: System Programming
Programming Horizontal Limits & Stow Position
The 8593-04 Copperhead RF monitor must show H2 limits relative to mounting

flange. The monitor is shipped from the factory with horizontal limits at 180° (90°

left and 90° right of the straight ahead position). The vertical limits are provided by

magnets placed in the monitor at assembly and are not adjustable.

NOTE: All programming steps must be completed. Otherwise the changes will not be

stored to permanent memory.

Remove the cover from the RF Receiver/Control Module located on the monitor.

Supply power to the monitor.

Hold the Red Programming Button on the control module board until the programming LED

flashes on (approx. 5 seconds).

To set the left travel limit, rotate the monitor left until it has reached the mechanical stop.

Quickly press and release the Red Programming Button. The status LED will flash once to

acknowledge the new limit position.

To set the right travel limit, rotate the monitor right until it has reached the mechanical stop.

Quickly press and release the Red Programming Button. The status LED will flash twice to

acknowledge the new limit position.

To set the horizontal stow position of the monitor, move the monitor left or right to the desired

position. Quickly press and release the Red Programming Button. The status LED will flash

rapidly several times to acknowledge the new stow position. NOTE: The stow position must be

between the right and left limits that were just programmed in the previous two steps. It is not

recommended to set the position right at the maximum right or left travel limit.

To choose the vertical stow position of the monitor, set switch A position 1 “ON” for stow up, or

switch A position 1 “OFF” for stow down (Receiver only). NOTE: The vertical stow position will

either be all the way up or all the way down, nowhere in between.

Remove power from the monitor for a minimum of 5 seconds. Reapply power and operate the

monitor to verify that the travel limits are at the correct positions, and the monitor stows

correctly. If not, follow the steps above to reprogram the limits.

Figure 3: SW1 Programming Button

Caution:

To prevent damage to the monitor controller, keep all metallic objects away

from the receiver circuit board while it is energized. Ensure all O-rings and gaskets are
properly installed when closing receiver enclosure.

DS5

DS2

B

A

DS1

SW4

SW1

DS4

P2

DS3

P3

DS6

P1

P4

SW2

SW3

Red Programming

Button (SW1)

Programming