beautypg.com

Test page – Despatch LAD Series WITH PROTOCOL PLUS User Manual

Page 43

background image

35

Test Page

The Test Page contains parameters which allow manual control of the heat control and
optional relay outputs and should be used only for testing the functionality of the control
instrument. Do not operate the oven for processes using the Test Page.

To access the Test Page, enter the Setup Mode (see description earlier in this manual).
Press the Page key until Test is displayed. Press the Menu key. Each parameter can be
changed by pressing the Menu key until the desired parameter is displayed, and then
pressing the

keys to change the value.


Menu Item

Display

Description

Range

Heater
output

Test HeatOut

Activate SSR output 100%

On

High limit
relay

Test HiLimOut

Activate high limit alarm
(de-energize relay)

On

Relay 1
output

Test Rly1 Out

Energize relay output 1

On

Relay 2
output

Test Rly2 Out

Energize relay output 2

On

Relay 3
output

Test Rly3 Out

Energize relay output 3

On

Relay 4
output

Test Rly4 Out

Energize relay output 4

On

HiLim
Sensor

Test HL Temp
(push and hold up)

Displays sensor reading*

*Push

key to refresh display


When the Test Page is entered, all outputs are automatically set to off. When exiting
the Test Page, all outputs will return to their previous condition regardless of the Test
Page settings.