Despatch Protocol Plus Modbus Communications User Manual
Page 18
Chromalox Instruments and Controls
A-51643 Rev. 6 10/06/03
12
421
1A5
Segment 4 Ramp Event 1-4 Setup
Seg-4 Ramp[Event1-4]
1 or 2 (Note 1) Bits 0-3 = Events 1-4. Bit value: 0 = Off, 1 = On
422
1A6
Segment 4 Soak Temp
Seg-4 Soak[Temp]
1 or 2 (Note 1) read/written as xxxx deg. F.
423
1A7
Segment 4 Soak Time
Seg-4 Soak[Time]
1 or 2 (Note 1) read/written as xx:xx hrs:min or min:sec
424
1A8
Segment 4 Soak Event 1-4 Setup
Seg-4 Soak[Event1-4]
1 or 2 (Note 1) Bits 0-3 = Events 1-4. Bit value: 0 = Off, 1 = On
425
1A9
Segment 5 Ramp Time
Seg-5 Ramp[Time]
1 or 2 (Note 1) read/written as xx:xx hrs:min or min:sec
426
1AA
Segment 5 Ramp Event 1-4 Setup
Seg-5 Ramp[Event1-4]
1 or 2 (Note 1) Bits 0-3 = Events 1-4. Bit value: 0 = Off, 1 = On
427
1AB
Segment 5 Soak Temp
Seg-5 Soak[Temp]
1 or 2 (Note 1) read/written as xxxx deg. F.
428
1AC
Segment 5 Soak Time
Seg-5 Soak[Time]
1 or 2 (Note 1) read/written as xx:xx hrs:min or min:sec
429
1AD
Segment 5 Soak Event 1-4 Setup
Seg-5 Soak[Event1-4]
1 or 2 (Note 1) Bits 0-3 = Events 1-4. Bit value: 0 = Off, 1 = On
430
1AE
Segment 6 Ramp Time
Seg-6 Ramp[Time]
1 or 2 (Note 1) read/written as xx:xx hrs:min or min:sec
431
1AF
Segment 6 Ramp Event 1-4 Setup
Seg-6 Ramp[Event1-4]
1 or 2 (Note 1) Bits 0-3 = Events 1-4. Bit value: 0 = Off, 1 = On
432
1B0
Segment 6 Soak Temp
Seg-6 Soak[Temp]
1 or 2 (Note 1) read/written as xxxx deg. F.
433
1B1
Segment 6 Soak Time
Seg-6 Soak[Time]
1 or 2 (Note 1) read/written as xx:xx hrs:min or min:sec
434
1B2
Segment 6 Soak Event 1-4 Setup
Seg-6 Soak[Event1-4]
1 or 2 (Note 1) Bits 0-3 = Events 1-4. Bit value: 0 = Off, 1 = On
435
1B3
Segment 7 Ramp Time
Seg-7 Ramp[Time]
1 or 2 (Note 1) read/written as xx:xx hrs:min or min:sec
436
1B4
Segment 7 Ramp Event 1-4 Setup
Seg-7 Ramp[Event1-4]
1 or 2 (Note 1) Bits 0-3 = Events 1-4. Bit value: 0 = Off, 1 = On
437
1B5
Segment 7 Soak Temp
Seg-7 Soak[Temp]
1 or 2 (Note 1) read/written as xxxx deg. F.
438
1B6
Segment 7 Soak Time
Seg-7 Soak[Time]
1 or 2 (Note 1) read/written as xx:xx hrs:min or min:sec
439
1B7
Segment 7 Soak Event 1-4 Setup
Seg-7 Soak[Event1-4]
1 or 2 (Note 1) Bits 0-3 = Events 1-4. Bit value: 0 = Off, 1 = On
440
1B8
Segment 8 Ramp Time
Seg-8 Ramp[Time]
1 or 2 (Note 1) read/written as xx:xx hrs:min or min:sec
441
1B9
Segment 8 Ramp Event 1-4 Setup
Seg-8 Ramp[Event1-4]
1 or 2 (Note 1) Bits 0-3 = Events 1-4. Bit value: 0 = Off, 1 = On
442
1BA
Segment 8 Soak Temp
Seg-8 Soak[Temp]
1 or 2 (Note 1) read/written as xxxx deg. F.
443
1BB
Segment 8 Soak Time
Seg-8 Soak[Time]
1 or 2 (Note 1) read/written as xx:xx hrs:min or min:sec
444
1BC
Segment 8 Soak Event 1-4 Setup
Seg-8 Soak[Event1-4]
1 or 2 (Note 1) Bits 0-3 = Events 1-4. Bit value: 0 = Off, 1 = On
445
1BD
High Limit SP
[Hi-Lim SP]
1 or 2 (Note 1) read/written as xxxx deg. F.
446
1BE
Loop From Segment #
[Loop From Seg No]
1 or 2 (Note 1) 0 = None; 1-8 = Loop from segement.
447
1BF
Loop to Segment #
[Loop To Seg No]
1 or 2 (Note 1) 0 = None; 1-8 = Loop to segement.
448
1C0
Loop # of Times
[Loop Number]
1 or 2 (Note 1) 0-99
449
1C1
Link to Profile
[Link To Pro]
1 or 2 (Note 1) -1=Stop, 0=Hold, 1-8=Profile 1-8, -2=Standby.
450
1C2
Guaranteed Soak Band
[Guar Band]
1 or 2 (Note 1) read/written as xxxx deg. F. 0 = Off.
Profile 2
451 -- 496
1C3 -- 1F0 Profile 2 Holding Registers (same as Profile 1)
1 or 2 (Note 1)
Profile 3
497 -- 542
1F1 -- 21E Profile 3 Holding Registers (same as Profile 1)
1 or 2 (Note 1)
Profile 4
543 -- 588
21F -- 24C Profile 4 Holding Registers (same as Profile 1)
1 or 2 (Note 1)
Profile 5
589 -- 634
24D -- 27A Profile 5 Holding Registers (same as Profile 1)
1 or 2 (Note 1)
Profile 6
635 -- 680
27B -- 2A8 Profile 6 Holding Registers (same as Profile 1)
1 or 2 (Note 1)
Profile 7
681 -- 726
2A9 -- 2D6 Profile 7 Holding Registers (same as Profile 1)
1 or 2 (Note 1)
Profile 8
727 -- 772
2D7 -- 304 Profile 8 Holding Registers (same as Profile 1)
1 or 2 (Note 1)
Auto Start Holding Registers
773
305
Auto Start Enable
Auto Start[Enable]
1 or 2 (Note 1) 0 = Disabled, 1 = Enabled