Install gas piping – Carlin 702GAS Inst Manual User Manual
Page 13

Model 702GAS Advanced gas burners — Instruction manual
Carlin part number MN702G Rev. 03/14/11
– 13 –
Where appliance instructions differ from this manual, follow the appliance instructions.
Table 3
Capacities of black iron pipe, cubic feet gas/hour
NATURAL GAS
Capacities in Cubic feet per hour
for Schedule 40 metal pipe
Pipe
size
(inches)
Total length of gas piping,
from meter to burner connection (feet)
20
40
60
80
100
Natural gas @ .60 specific gravity, pressure drop 0.3 in. w.c.
(note 1)
1¼
730
500
400
350
305
1½
1,100
760
610
530
460
2
2,100
1,450
1,150
990
870
2½
3,300
2,300
1,850
1,600
1,400
Natural gas @ .60 specific gravity, pressure drop 0.5 in. w.c.
(note 1)
1¼
950
660
530
460
400
1½
1,460
990
810
690
620
2
2,750
1,900
1,520
1,300
1,150
2½
4,350
3,000
2,400
2,050
1,850
Note 1
For natural gas with specific gravity other than 0.60,
consult National Fuel Gas Code for correction factor.
PROPANE GAS
Capacities in Btuh for
Schedule 40 metal pipe
Pipe size
(inches)
Total length of gas piping,
from meter to burner connection (feet)
20
40
60
80
100
Propane gas @ 1.5 specific gravity, pressure drop 1 psi
½
1,839
1,264
1,015
869
770
¾
3,845
2,643
2,122
1,816
1,610
1
7,243
4.978
3,998
3,422
3,033
Propane gas @ 1.5 specific gravity, pressure drop 0.5 in. w.c.
1
787
541
434
372
330
1¼
1,616
1,111
892
677
543
1½
2,422
1.664
1,337
1,114
1,014
Figure 8 Gas train pressure drop
3. Install gas piping
(continued)
Regulator spring:
The standard main gas pressure regulator spring (see
item 8, Figure 7, page 12) is plated. The range is from
3.0 to 6.0 inches water column.
The 1” RV61 regulator is available with an optional
blue spring, with a range of 5.0 to 12.0 inches water
column.
The 1¼” or 1½” RV81 regulator is available with the
standard plated spring (3.0 to 6.0 inches water column)
or a violet spring, with a range of 4.0 to 12.0 inches
water column.
PROPANE applications — A brown spring (1.0” to
3.5” w.c. range) may be required for propane.