Programming, Program parameters, 4 programming – Carbolite 302P4 User Manual
Page 10

Programming
10
MC22 -GB-v1.01
4 Programming
4.1
Program Parameters
In the basic operator mode
– the below list of parameters are available.
nPrg
Meaning:
number of the selected program
Range:
from 1 to 3 fixed and password protected. Program 4 editable
Available:
Always
Alterable:
only when the programmer state is idle
Seg
Meaning:
number of the segment in execution
Range:
from “1 r” to “4 d”
The segment number is followed by the segment stage, “r” for ramp
and “d” for dwell. Example:
1 r:
ramp stage of the first segment
4 d:
dwell stage of the fourth segment
Available:
only when the programmer state is run or hold
Alterable:
never
rt.
Meaning:
time remaining to the end of the program
This value refers to the time remaining to the end of the current
execution, regardless the programmed number of executions.
Range:
- from 1 second to 99 min 59 sec
the upper display shows 12.30 (12 min 30 sec)
the lower display shows rt.S
- from 1 h 40 min to 99 h 59 min
the upper display shows 18.45 (18 h 45 min)
the lower display shows rt.H
- from 100 to 9999 hours
the upper display shows
125 (125 h)
the lower display shows rt.H
- over 9999 hours
the upper display shows %%%%
the lower display shows rt.H
Available:
only when the programmer state is run or hold
Alterable:
never