Led t8 tubes – American Lighting LT8-48XX-PRO Series User Manual
Page 3

11. Attach lead wires from new sockets to supply wires, making sure to match polarity (connect black to black and white to white),
using appropriate UL Listed wire nuts. See Figure 8.
12. Cut back any remaining wires from the socket(s) at the “dead end” and cap off with a UL Listed wire nut. Leave this socket
in place to hold the LED T8 Tubes. See Figure 9.
13. Replace ballast cover.
14. Attach warning sticker to ballast cover in a conspicous spot for reference: “This fixture has been modified - the ballast has
been removed. Do not install fluorescent lamps in this fixture!!”
15. Replace any lenses that were removed.
16. Turn back on power supply.
www.americanlighting.com
RV-1210
Figure 8
Figure 9
Attach lead wires from
sockets to supply wires,
making sure to match
polarity (connect black to
black and white to white.)
NON-SHUNTED SOCKET INSTALLATION AND FIXTURE MODIFICATION (continued from previous page)
Cut back remaining
wires and cap off. Leave
the sockets at the dead
end in place to hold the
LED T8 Tubes.
REFERENCE BEFORE AND AFTER FOR A RETROFIT FOR T8 TUBES INTO A BALLASTED T8 LUMINAIRE
BEFORE (WITH BALLAST AND ORIGINAL LAMPHOLDERS)
AFTER (WITH BALLAST REMOVAL AND NON-SHUNTED LAMPHOLDERS) INSTALLATION AT LIVE END
FUTURE LAMP REPLACEMENT
Model T8-L1200-18W-02-277-XX (4-foot LED T8 Tubes) is available from American
Lighting in case quantities. Contact 800-880-1180 or visit www.americanlighting.com
to find a local distributor.
Please note that the American Lighting part number LT8-48XX-PRO is also known as
T8-L1200-18W-02-277-XX where XX denotes color temperature:
32 = 3200K
41 = 4100K
55 = 5500K
.
Model Number
LED Qty
Voltage
Hz
Wattage
Input Current
T8-L1200-18W-02-277
264
100-277V AC
60
18W
150mA
THE END RETROFIT LUMINAIRE HAS BEEN MODIFIED AND CAN NO LONGER
OPERATE THE ORIGINAL INTENDED LAMP(S).
LED T8 Tubes
Installation instructions for T8-L1200-18W-02-277-XX Series (LT8-48XX-PRO Series)