beautypg.com

High-low fire option – Aerovent IM-200 User Manual

Page 4

background image

Units ordered with the high-low fire option are supplied with

a 1" NPT SR600 two-stage valve mounted in the pipe train.

The SR600 provides an economical means of flame staging

where infinite modulation is not required. Turn-down on low-

fire is from 25% to 75% of high-fire. This valve is powered by

a 24 volt AC transformer. When the coil is energized, the valve

is at low-fire. When the coil is de-energized, it is at high-fire.

Adjustments

To check the minimum or low-fire and maximum or high-fire

pressures for the limits of modulation or staging, use the fol-

lowing procedures:

To set minimum or low-fire
1. Remove the cover plate 1.
2. Remove the high fire adjusting screw 2, spring 3, and

plunger 4. A small magnet is useful for this purpose.

Handle the plunger carefully to avoid marring or collecting

dirt. Do not lubricate.

3. Modulation or Staging: Using the low-fire adjusting screw

5

, set the manifold pressure to the manufacturer’s specifi-

cations (50% to 75% of high-fire).

4. Modulation or Staging: Cycle the solenoid gas valve to

check for proper ignition.

5. Modulation or Staging: Adjust the air shutter or increase

low-fire adjustment if needed.

6. Replace the plunger, spring and high-fire adjusting screw.

To set maximum or high-fire:
Note:
To avoid danger of over-firing, make certain that the

inlet pressure is at 1.0" w.c. above the outlet pressure.
1. Modulation and Staging: Using the high-fire adjusting

screw 2, set the manifold pressure to the manufacturer’s

specifications. See page 1, Fig. 1.

2. Staging Only: Cycle the burner to check performance.
3. Replace the cover plate.

High-Low Fire Option

Make sure plunger

is installed as

above.

Aerovent | www.Aerovent.com

5959 trenton Lane n | minneapolis, mn 55442 | Phone: 763-551-7500 | Fax: 763-551-7501

®