beautypg.com

Aerovent IM-200 User Manual

Page 3

background image

IM-200

3

overhead door. Normal operation is to leave the on-off switch

“on” and cycle the unit with the door switch as the overhead

door on the dock opens and closes.

Door opening closes the switch between terminal #1 and

#3; the fan starts. Interlock (E) on the fan starter (FSR) closes

the circuit between terminal #6 and #7. An electrical circuit is

made to terminal #7 through the high gas pressure switch (C)

and airflow switch (D). Power on terminal #7 will cause the

primary combustion relay (RM7890) to pull in. Ignition occurs

powered from terminal #9, main gas valves open powered

from terminal #11.

Flame is proven through the flame rod and the RM7890

primary relay allows power to energize terminal #10 and de-

energizes terminal #9 dropping out the ignition transformer.

If discharge temperature exceeds 200°F, high limit (A)

between terminals #10 and #11 will open which de-energizes

the gas valves. Loss of flame will cause combustion relay to

lock out requiring manual reset on IRI, FM single valve and

1. Switch the on-off toggle switch to the “ON” position in

remote station. The indicator light should come on. If not,

check the power supply to the unit, the fuse between H and

XI or the bulb to see if it has burned out.

2. Close the door switch between terminal #1 and #3. The

fan should start. If not, check overload on the motor

starter (manual reset) when the fan starts auxiliary contact

between terminal #6 and #7 closes. You should have 120

volts to terminal #7 (flame relay). If not, check the high gas

pressure switch (manual reset) or the airflow switch. The

high gas pressure switch should be set at 21.0". The airflow

switch should be set at 1.0".

3. When the flame relay has power to terminal #6, it will go

through a self-checking cycle and then power wire #9 from

terminal #10, turning on the ignition transformer and wire

#10 from terminal #8, opening the main valves. If ignition

(spark) is occurring but valves do not open, check the high

limit between terminal #10 and #11. High limit should be

set at 200°F. If spark is not occurring, check the spark plug.

The gap should be 0.072 and the electrode should be clean

(no carbon). If the flame relay has power to it but flame

cycle will not occur, reset the flame relay (manual reset). If

flame comes on momentarily and goes out, check the flame

rod. There should not be any cracks in the porcelain. The

flame rod senses current in the flame. To check if it is

functioning, plug a voltmeter into the amplified module.

The unit should be 0-5 volts D.C. (On older units equipped

with RA890F, a test jack is beside the red reset button and

the unit should be minimum 2 microamps. Normal range

is 2-5 microamps.)

4. IRI and FM units work the same as standard with the

exception that they have a pilot which lights before the

main flame comes on. If the pilot does not light, check to

see that the

1

4

" pilot valve is opening, the pilot gas line is

not obstructed or the pilot assembly in the burner is intact.

Also, there is a timer to turn the pilot off after the burner

lights which should be set at approximate 5 seconds. Check

the timer to make sure it is functioning.

5. Some units are supplied with a UV scanner (mini-peeper)

rather than a flame rod. Flame current check should yield

the same results as a flame rod: 0-5 volts D.C. (on older

units equipped with RA890G flame relay, flame current

should be minimum 1.5 microamps).

For additional troubleshooting guidance, refer to

RM7890A1015 bulletin.

FM 2 valve. The standard unit will try to restart on flame loss.

The sequence of operation is similar for IRI and FM units.

For schematic wiring, see the following reduction drawings:

Standard . . . . . . . . . . . . . . . . . R26871-00

IRI . . . . . . . . . . . . . . . . . . . . . R26870-00

FM Single Valve. . . . . . . . . . . R26870-00

FM Two Valve . . . . . . . . . . . . R26869-00

All Piping Diagrams . . . . . . . R26872-00

Standard Wiring and Piping Sequence of Operation

Troubleshooting