Door switch and suggested installations – Aerovent IM-200 User Manual

Page 2

background image

2

IM-200

5. Mount the door switch so it will trip to close the circuit

when the door is open. The switch may be located so the

heater will come on when the door starts to open or when

fully open at the discretion of the user. See typical sug-

gested installations.

Door Switch and Suggested Installations

The door switch may be installed with the switch in the “free”

position when the door is either opened or closed. If the

switch is mounted so that it is in the “free” position when the

door is open, use the normally-closed circuit, terminals #1 and

#2. If the switch is mounted so that it is in the “free” position

when the door is closed, use the normally-open circuit, termi-

nals #3 and #4.
Installation #1: Floor Level Location - Switch is in “free”

position when the door is open. Use switch terminals #1 and

#2. Heater will fire when the door starts to open.
Installation #2: Overhead Location - Switch is in “free” posi-

tion when the door is closed. Use switch terminals #3 and #4.

Heater will fire only when the door is completely open.
Installation #3: Overhead Location - Switch is in “free” posi-

tion when the door is open. Use switch terminals #1 and #2.

Heater will fire when the door starts to open.
The unit can be operated manually with an on-off switch in

remote station or automatically from a door switch on an

“FREE” POSITION: 360°

location on actuator shaft

ACTUATOR

SHAFT

OPERATING

HEAD: May be

relocated four

90° positions.

LEVER LOCKING

NUT: Loosen to

to relocate “free”

position of adjustable

roller lever.

TERMINAL

CONNECTIONS:

#1 & #2 Normally

Closed

#3 & #4 Normally

Open

DOOR SWITCH

CLAMP PLATE

ALLENHEAD SCREW:

Loosen to adjust radius

of roller lever.

1

3

16

" Min.

3" Max.

49°

49°

ADJUSTABLER

ROLER LEVER

MAXIMUM

TRAVEL

Door

Door

Track

Door

Switch

Actuated Position

Free Position

49° Max.

15° Min.

INSTALLATION

NO. 3

INSTALLATION

NO. 1

INSTALLATION

NO. 2

OIL TIGHT DOOR SWITCH

Connect to terminal 1 and 3 on terminal strip

in unit control box.
Connect as shown when switch is released

with door in open position.

Connect as shown when switch is held with

door in open position.