beautypg.com

Aerovent IM-301 User Manual

Page 2

background image

2

Aerovent IM-301

2.2 LIFTING

AXIAD fans should be lifted using slings. Note that on

AXIAD fans the slings should be placed under the skids, and

the spreader bars used as required. Under no circumstances

should the vane section be used for lifting.
2.3 MOUNTING

Depending on the type of fan support specified, the

fan can either be horizontally floor mounted on legs, horizon-

tally supported on a structural frame, horizontally ceiling hung

with clips or support brackets, vertically floor mounted on a

frame, or vertically ceiling hung.
2.3.1 Vibration Isolators

The fan is dynamically balanced to reduce vibration to

a low level. However, it is recommended that the fan be sup-

ported on vibration isolators. Isolators should be selected for

each installation in accordance with individual requirements.

The weight distribution between mounts is not equal

on AXIAD II fans. Consult the factory for isolator selection

or mount loads. Isolators should be selected to support the

unequal load with equal deflection. A subbase can be used to

equally distribute the load to the isolators. Concrete inertia

pads are generally not required on axial fans.
2.3.2 Fan Reactions

It is essential to minimize fan movement due to starting

torque and air thrust force. These forces must be resisted to

maintain duct alignment and prevent damaging the flexible

connectors. Isolators must be selected with adequate stiffness

to resist these forces. Snubbers may be required in some instal-

lations to limit the fan movement.
2.4 DUCT CONNECTIONS

All fans should be closely aligned with the ductwork. A

flexible connection should be provided between the fan and

duct to prevent structure-borne noise from being transmitted

to the ductwork. Use band clamps and seal with Borden’s

Arabol, or equal, to insure mechanical security and prevent

leakage on all flexible connections.

NOTE: Provide a 1-inch to 2-inch gap between the fan

and duct to allow for fan movement.
2.4.1 Diffuser and Cone Connection

On AXIAD II fans, the discharge cone and diffuser

can be directly connected to the fan and thus become a part

of the load to be isolated. On Arrangement 4 Type 2 AXIAD

fans inlet cones can be directly connected and they also

become part of the load to be isolated.
2.4.2 Inlet Bell Connection

The inlet bell may be mounted in a plenum wall with a

flexible connection between the outer edge of the bell and a

hole in the partition. Provide a 2-inch to 3-inch gap to allow

for fan movement.

The inlet bell may be installed protruding into the ple-

num where space is limited. A metal ring should be installed

between the inlet bell and the case flange and a flexible con-

nection installed between the ring and the plenum wall.
2.5 ELECTRICAL

All wiring should conform to local electrical codes and

the job specification. In NEMA standard MG-2, NEMA

addressed the phenomena of transient torques. We advise that

measures be taken to protect your equipment from transient

torque and power interruptions.

2.5.1 Power Connection

The motor leads terminate in the conduit box. The

leads are factory connected for the voltage specified for the

job. Motor leads for wye-delta and part-winding starts are not

connected. Rigid conduit should be run from the motor

starter to the fan with a short section of flexible conduit at the

conduit box to allow for fan movement.

Wire size and motor overloads should be sized in

accordance with the fan nameplate electrical data. The conduit

box is located on the outside of the case on all ducted, direct

driven fans. If the motor is outside the fan case, connection

will be made directly to the motor.
2.5.2 Motor Rotation

Check motor rotation by jogging the motor. The rota-

tion should be clockwise when viewed from the inlet of the

fan. Reverse any two motor leads to change rotation.

NOTE: It is important that correct motor rotation be

established on ducted fans as the rotor will not be visible after

an inlet duct is installed.
2.5.3 Electrical Data

The fan should be started in accordance with Section

2.5.4 and the electrical data measured and compared to motor

nameplate ratings.
2.5.4 Final Check Before Putting

Fan Into Operation

1. Check for correct supply voltage and motor overloads.
2. Insure that all loose debris is removed from fan, fan room,

plenum and/or all ducts.

3. Check that motor bolts are tight and rotor is centered in fan

case with adequate blade tip clearance all- around.

4. Hand rotate and then bump the fan starter to check rota-

tion.

5. Start the fan and verify that the vibration is acceptable.

3.0 AXIAD II FAN BLADE ADJUSTMENT

3.1 GENERAL

The AXIAD II FTFA fan is an adjustable pitch fan.

The blade pitch has been factory set to meet the airflow

requirement of the job specification. The pitch may be

changed to meet other airflow requirements on the jobsite.

Each blade has cast into it a number of raised marks with

grooves in between and the fairing has a register mark

machined into it at each blade opening. See Figure 2, which

identifies each of the ridges and grooves with a number from

0 to 9. These numbers correspond to the performance curve

numbers shown in the AXIAD II design performance manual.