Minimum safe approach distance -ii, Table 1 - (m.s.a.d.) -ii, Figure 1 - (m.s.a.d.) -ii – Snorkel SP18 User Manual
Page 4: Electrical hazard

page - ii
SP17/SP18 – 11972A
Electrical Hazard
■ Minimum Safe Approach Distance
An SP is an all metal NOT ELECTRICALLY INSULATED, aerial work platform. DO NOT operate it near
ELECTRICAL conductors. Regard all conductors as being energized. Use the table and illustration below
to determine safe clearance from electrical conductors. (Table 1 and Figure 1, below, are from ANSI/SIA
A92.6–1990 Standard, reprinted with permission of Scaffold Industry Association.)
❑
Table 1 - (M.S.A.D.)
Minimum Safe Approach Distance
to energized (exposed or insulated power lines)
Voltage range
Minimum safe approach distance
(phase to phase)
(Feet)
(Meters)
0 to 300V
Avoid contact
over 300v to 50kv
10
3.05
over 50kv to 200kv
15
4.60
over 200kv to 350kv
20
6.10
over 350kv to 500kv
25
7.62
over 500kv to 750kv
35
10.67
over 750kv to 1000kv
45
13.72
❑
Figure 1 - (M.S.A.D.)
Denotes
prohibited
zone