Page 4 of 5 pages, Four output tank level – Class1 4 output tank level User Manual
Page 4
page 4 of 5 pages
Engineering
Standards
Name
Identifier
OEM Installation and Calibration
Engineering Standard Number
C1-105593
Four Output Tank Level
ISO 9001 CERTIFIED
E:\
MANUALS
\
DIGITAL
\
TANKLEVEL
\N
EW
T
ANK
L
EVEL
_ESN.
P
65_05062001
Level Calibration
For Level Calibration, enter the following password
EMPTY
EMPTY
EMPTY
EMPTY
EMPTY
FULL
EMPTY
FULL
Press and hold both calibration switches for two (2)
seconds. Both calibration LED’s will illuminate.
Release both switches. Both calibration LED’s will
flash as well as the Full output and the 1/4 tank output.
With the tank either empty or full,
p r e s s
the switch associated with the condition of the tank (empty
or full) that you are calibrating. The LED, Output and the
COM LED will come on for 1/2 second and then go out.
The opposite calibration LED, output and the COM LED will
flash at a rate of once per second.
Press the switch associated with the flashing cali-
bration LED. The flash rate will increase.
Either empty or fill the tank as appropriate. Allow
the water level to stabilize and then press the calibration
switch under the flashing LED. (hold for 1/2 second) Both
calibration LED’s will come on steady, The outputs will indi-
cate the current tank level and the COM LED will return to a
steady green.
REVB
AMS
P.N. 105299
8-24-2000
R17
R14
LED3
LED2
C15
FT3
XT1
U12
U11
U2
U1
TP3
TP2
TP1
R23 R13
R12
R11
R10
R5
R3 R2
LED1
C12
C11
C2
C1
U13
C3
C5
U6
C10
D2
D3
R6 R7
R8
R9
R20
R21
R22
SW2
SW3
U4
U5
U10
CONN1
C4
+
F1
Z1
U9
EMPTY
FULL
CALIBRATE
LED3
LED2
SW2
SW3
EMPTY
FULL
CALIBRATE
LED3
LED2
SW2
SW3
EMPTY
FULL
CALIBRATE
Pressed
Not Pressed
OFF
ON
Flash
Press and hold both switches
for two (2) seconds.
Both LED's will illuminate.
LED3
LED2
SW2
SW3
EMPTY
FULL
CALIBRATE
Release both switches.
Both LED's will Flash at
the same time.
LED3
LED2
SW2
SW3
EMPTY
FULL
CALIBRATE
LED3
LED2
SW2
SW3
EMPTY
FULL
CALIBRATE
LED3
LED2
SW2
SW3
EMPTY
FULL
CALIBRATE
LED3
LED2
SW2
SW3
EMPTY
FULL
CALIBRATE
LED3
LED2
SW2
SW3
EMPTY
FULL
CALIBRATE
Press the switch for the
calibration you will perform
first. (Full or Empty)
You can start with either, this
example will use FULL.
The FULL LED will start to
flash rapidly. The EMPTY
LED should turn off.
With the tank filled, press the
FULL calibration switch for 1/2
second.
The FULL LED will turn on steady
for 1/2 second and then turn off.
The EMPTY LED will start flashing
at a rate of once per second.
Press the EMPTY switch. The flash
rate will increase.
Empty the tank and then press the
EMPTY switch again.
LED3
LED2
SW2
SW3
EMPTY
FULL
CALIBRATE
The EMPTY LED will come on steady
for 1/2 second and then both LED's will
turn on steady and then turn off.
The outputs will indicate the current
tank level.
Level Calibration is complete.