OEM Installation and Calibration

Engineering Standard Number

C1-105593

Four Output Tank Level

ISO 9001 CERTIFIED

E:\

MANUALS

\

DIGITAL

\

TANKLEVEL

\N

EW

T

ANK

L

EVEL

_ESN.

P

65_05062001

Level Calibration

For Level Calibration, enter the following password

EMPTY

EMPTY

EMPTY

EMPTY

EMPTY

FULL

EMPTY

FULL

Press and hold both calibration switches for two (2)

seconds. Both calibration LED’s will illuminate.

Release both switches. Both calibration LED’s will

flash as well as the Full output and the 1/4 tank output.

With the tank either empty or full,

p r e s s

the switch associated with the condition of the tank (empty
or full) that you are calibrating. The LED, Output and the
COM LED will come on for 1/2 second and then go out.
The opposite calibration LED, output and the COM LED will
flash at a rate of once per second.

Press the switch associated with the flashing cali-

bration LED. The flash rate will increase.

Either empty or fill the tank as appropriate. Allow

the water level to stabilize and then press the calibration
switch under the flashing LED. (hold for 1/2 second) Both
calibration LED’s will come on steady, The outputs will indi-
cate the current tank level and the COM LED will return to a
steady green.

REVB

AMS

P.N. 105299

8-24-2000

R17

R14

LED3

LED2

C15

FT3

XT1

U12

U11

U2

U1

TP3

TP2

TP1

R23 R13

R12

R11

R10

R5

R3 R2

LED1

C12

C11

C2

C1

U13

C3

C5

U6

C10

D2

D3

R6 R7

R8

R9

R20

R21

R22

SW2

SW3

U4

U5

U10

CONN1

C4

+

F1

Z1

U9

EMPTY

FULL

CALIBRATE

LED3

LED2

SW2

SW3

EMPTY

FULL

CALIBRATE

LED3

LED2

SW2

SW3

EMPTY

FULL

CALIBRATE

Pressed
Not Pressed

OFF

ON

Flash

Press and hold both switches
for two (2) seconds.
Both LED's will illuminate.

LED3

LED2

SW2

SW3

EMPTY

FULL

CALIBRATE

Release both switches.
Both LED's will Flash at
the same time.

LED3

LED2

SW2

SW3

EMPTY

FULL

CALIBRATE

LED3

LED2

SW2

SW3

EMPTY

FULL

CALIBRATE

LED3

LED2

SW2

SW3

EMPTY

FULL

CALIBRATE

LED3

LED2

SW2

SW3

EMPTY

FULL

CALIBRATE

LED3

LED2

SW2

SW3

EMPTY

FULL

CALIBRATE

Press the switch for the
calibration you will perform
first. (Full or Empty)
You can start with either, this
example will use FULL.

The FULL LED will start to
flash rapidly. The EMPTY
LED should turn off.

With the tank filled, press the
FULL calibration switch for 1/2
second.

The FULL LED will turn on steady
for 1/2 second and then turn off.
The EMPTY LED will start flashing
at a rate of once per second.

Press the EMPTY switch. The flash
rate will increase.

Empty the tank and then press the
EMPTY switch again.

LED3

LED2

SW2

SW3

EMPTY

FULL

CALIBRATE

The EMPTY LED will come on steady
for 1/2 second and then both LED's will
turn on steady and then turn off.
The outputs will indicate the current
tank level.
Level Calibration is complete.