Engineering standards, Page 2 of 5 pages, Tank level gauge transducer installation – Class1 4 output tank level User Manual

Page 2

background image

page 2 of 5 pages

Engineering

Standards

Name

Identifier

OEM Installation and Calibration

Engineering Standard Number

C1-105593

Four Output Tank Level

ISO 9001 CERTIFIED

E:\

MANUALS

\

DIGITAL

\

TANKLEVEL

\N

EW

T

ANK

L

EVEL

_ESN.

P

65_05062001

The transducer measures the column of water in the tank above the opening of the elbow.
When calibrating for a full tank it is important that the tank not be overfilled. If the fill opening or
tank vent is above the transducer, care should be taken not to have water in this area when
calibrating the tank level gauge. The transducer should never be mounted in the sump area
because of sludge and potential inaccuracies in calibration.

Mount a 3/4 NPT elbow just off the bottom of the tank, enough to keep sediment out of the
elbow and transducer (

PN 102162

). Attach a 3/4 to 1/4 NPT adapter (supplied for foam) to the

elbow and mount the transducer to that. The elbow and adapter need to be installed so that
the transducer is mounted vertically.

Harness

Pressure Transducer
1/4 NPT

Adapter 3/4-1/4 NPT Bushing (OEM)
Foam adapter is supplied when a
foam level system is ordered.

3/4 NPT Elbow (OEM)

FLUID TANK

Tank Level Gauge

Transducer Installation

The transducer must be mounted vertically as depicted to insure an accurate and reliable reading.
This will also prevent damage to the transducer from freezing.
Harnesses are supplied with a cable to connect the transducer.
Loose wires with appropriate terminals for the outputs and ground are including to facilitate installation.

5’ PN 105597
10’ PN105598
20’ PN105599