Outdoor sound: octave band data - decibels, Physical data – Bryant 601A User Manual
Page 4

—4—
OUTDOOR SOUND: OCTAVE BAND DATA - DECIBELS
dB — Sound Level (decibels)
PHYSICAL DATA
* Air filter pressure drop for non-standard filters must not exceed 0.08 in. wg.
ELECTRIC HEAT PRESSURE DROP TABLES
Small Cabinet: 018-042
Large Cabinet: 048-060
MODEL NO.
601A
Frequency (Hz)
018
024
030
036
042
048
060
63
42.6
48.9
41.0
58.9
50.4
56.7
57.1
125
56.0
55.0
65.7
66.1
58.2
64.2
63.2
250
62.4
59.2
66.6
66.5
60.5
70.5
68.0
500
63.9
63.6
66.2
71.3
66.0
73.8
71.3
1000
65.4
65.6
67.7
72.9
66.8
74.0
72.3
2000
64.7
64.3
65.3
70.9
64.1
71.3
70.1
4000
62.6
63.5
62.1
66.1
61.8
68.9
67.4
8000
54.4
57.7
56.2
58.6
53.0
60.9
61.0
UNIT SIZE 601A
018
024
030
036
042
048
060
NOMINAL CAPACITY (ton)
1-1/2
2
2-1/2
2-1/2
3-1/2
4
5
OPERATING WEIGHT (lb)
283
289
287
291
323
353
418
COMPRESSORS
1
Quantity
1
TYPE
RECIPROCATING COMPRESSOR
SCROLL COMPRESSOR
REFRIGERANT*
R-22
REFRIGERANT METERING DEVICE
Accurater
Refrigerant (R-22) Quantity (lb.)
6.5
5.3
5.6
7.6
8.0
7.85
9.3
ORIFICE ID (in.)
0.053
0.061
0.068
0.078
0.078
0.088
0.093
ORIFICE ID (in.)
0.040
OUTDOOR COIL
Rows—Fins/in.
Face Area (sq ft)
1—17
10.2
1—17
12.0
1—17
12.0
2—17
10.3
2—17
10.3
2—17
11.6
2—17
11.6
OUTDOOR FAN
Nominal Airflow (Cfm)
Diameter
Motor Hp (Rpm)
2400
22
1/8 (825)
2400
22
1/8 (825)
2400
22
1/8 (825)
2800
22
1/4 (1100)
2400
22
1/8 (825)
3300
22
1/4 (1100)
3300
22
1/4 (1100)
INDOOR COIL
Rows—Fins/in.
Face Area (sq ft)
2—15
3.7
2—15
3.7
3—15
3.7
3—15
3.7
4—15
3.7
3—15
4.7
4—15
4.7
INDOOR BLOWER
Nominal Airflow (Cfm)
Size (in.)
Motor Hp (Rpm)
700
10 x 10
1/4 (825)
800
10 x 10
1/4 (1050)
1000
10 x 10
1/4 (1050)
1200
11 x 10
1/2 (1075)
1250
11 x 10
3/4 (1075)
1600
11 x 10
3/4 (1075)
2000
11 x 10
1 (1100)
RETURN-AIR FILTERS (In.)*
Throwaway
20 x 20 x 1
20 x 20 x 1
20 x 20 x 1
20 x 24 x 1
24 x 30 x 1
24 x 30 x 1
24 x 30 x 1
STATIC
CFM
500
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
5 Kw
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.02
0.04
0.06
0.07
10 Kw
0.00
0.00
0.00
0.00
0.00
0.02
0.04
0.06
0.07
0.09
0.10
0.11
15 Kw
0.00
0.00
0.00
0.02
0.04
0.06
0.08
0.10
0.12
0.14
0.16
0.18
20 Kw
0.00
0.00
0.02
0.04
0.06
0.08
0.09
0.11
0.13
0.15
0.17
0.19
STATIC
CFM
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
5 Kw
0.00
0.00
0.00
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
10 Kw
0.00
0.00
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.13
15 Kw
0.00
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.13
0.14
0.15
20 Kw
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.13
0.14
0.15
0.16
3 2
5
A2
M
A
N
U
F
A
C
T
U
R
E
R
CE
RT
IFIED
TO ARI
AS
C
O
M
P
L
Y
IN
G
W
IT
H
A
RI
STANDARD
24
0
U
N
IT
A
R
Y
HE
A
T
P
U
M
P
EQUIPMENT
®