PERFORMANCE DATA (cont)
COOLING EXTENDED PERFORMANCE TABLE
HEATING EXTENDED PERFORMANCE TABLE
-10–20
HEATING EXTENDED PERFORMANCE TABLE 30–60
*At 75°F entering dry bulb—Tennessee Valley Authority [TVA] rating conditions; all others at 80°F entering dry bulb.
See Legend and Notes on page 18.
601A036 (3 TONS)
Temp (F)
Air Ent
Outdoor Coil
(Edb)
Indoor Entering Air—CFM/BF
1050/0.10
1200/0.13
1350/0.17
Indoor Entering Air—Ewb (F)
72
67
63*
62
72
67
63*
62
72
67
63*
62
85
TC
39.4
36.0
33.2
32.3
39.5
36.6
33.9
33.1
40.0
37.1
34.2
33.7
SHC
19.3
24.5
23.7
29.1
19.8
25.9
25.0
30.9
20.4
27.2
26.3
32.4
kW
3.43
3.38
3.29
3.31
3.50
3.45
3.38
3.40
3.58
3.54
3.45
3.48
95
TC
38.1
34.3
31.6
30.7
38.5
35.0
32.2
31.5
39.1
35.5
32.6
32.1
SHC
18.9
23.9
23.0
28.3
19.6
25.3
24.4
30.1
20.4
26.8
25.7
31.6
kW
3.67
3.59
3.48
3.50
3.75
3.68
3.58
3.60
3.83
3.77
3.65
3.68
105
TC
36.4
32.6
30.0
29.1
36.9
33.2
30.5
29.8
37.5
33.6
30.7
30.5
SHC
18.3
23.2
22.4
27.5
19.0
24.7
23.8
29.1
19.9
26.0
24.9
30.4
kW
3.91
3.80
3.69
3.69
3.99
3.89
3.78
3.79
4.07
3.98
3.85
3.89
115
TC
34.5
30.8
28.2
27.3
35.1
31.3
28.5
28.2
35.5
31.7
28.9
29.1
SHC
17.6
22.5
21.6
26.6
18.5
24.0
23.0
28.2
19.2
25.4
24.3
29.1
kW
4.13
4.01
3.88
3.90
4.23
4.11
3.98
4.01
4.31
4.19
4.06
4.10
601A036 (3 TONS)
Temp (F)
Indoor Air Cfm (std)
Air Temperature Entering Outdoor Coil (F db at 70% rh)
Ent Indoor Coil
-10
0
10
17
20
60
1050
TC
6.06
5.61
11.03
10.20
15.93
15.06
19.38
17.65
20.91
18.80
kW
2.28
2.45
2.61
2.72
2.77
1200
TC
6.26
5.79
11.32
10.47
16.31
15.40
19.86
18.13
21.35
19.24
kW
2.35
2.50
2.66
2.76
2.82
1350
TC
6.46
5.97
11.61
10.74
16.69
15.73
20.24
18.42
21.78
19.67
kW
2.41
2.56
2.71
2.81
2.86
70
1050
TC
5.28
4.88
10.07
9.32
14.87
14.01
18.23
16.60
19.67
17.75
kW
2.29
2.48
2.67
2.79
2.85
1200
TC
5.52
5.10
10.41
9.63
15.25
14.39
18.71
17.08
20.10
18.13
kW
2.36
2.53
2.72
2.84
2.89
1350
TC
5.76
5.32
10.75
9.94
15.64
14.77
19.09
17.37
20.53
18.52
kW
2.42
2.59
2.76
2.89
2.94
80
1050
TC
4.14
3.83
8.90
8.23
13.62
12.86
16.98
15.45
18.42
16.89
kW
2.28
2.49
2.71
2.86
2.93
1200
TC
4.46
4.12
9.25
8.55
14.06
13.24
17.65
16.12
18.85
17.13
kW
2.35
2.55
2.76
2,90
2.97
1350
TC
4.77
4.41
9.59
8.87
14.49
13.62
17.84
16.31
19.28
17.37
kW
2.42
2.61
2.81
2.95
3.01
601A036 (3 TONS)
Temp (F)
Indoor Air Cfm (std)
Air Temperature Entering Outdoor Coil (F db at 70% rh)
Ent Indoor Coil
30
40
47
50
60
60
1050
TC
25.81
22.64
31.37
31.37
35.98
35.98
37.42
37.42
41.73
41.73
kW
2.94
3.12
3.28
3.31
3.43
1200
TC
26.58
23.22
31.95
31.95
36.55
36.55
37.61
37.61
42.31
42.31
kW
2.96
3.15
3.29
3.33
3.46
1350
TC
26.86
23.60
32.43
32.43
36.65
36.65
37.70
37.70
43.08
43.08
kW
3.01
3.18
3.30
3.33
3.51
70
1050
TC
24.46
21.39
29.93
29.93
34.54
34.54
36.07
36.07
41.54
41.54
kW
3.04
3.24
3.42
3.47
3.66
1200
TC
24.85
21.87
30.51
30.51
35.21
35.21
36.75
36.75
42.02
42.02
kW
3.06
3.26
3.43
3.49
3.66
1350
TC
25.52
22.35
31.08
31.08
35.79
35.79
36.75
36.75
42.12
42.12
kW
3.11
3.30
3.46
3.48
3.69
80
1050
TC
23.22
20.34
28.40
28.40
33.00
33.00
34.54
34.54
41.35
41.35
kW
3.14
3.36
3.55
3.61
3.90
1200
TC
23.89
20.82
29.17
29.17
33.67
33.67
35.21
35.21
41.54
41.54
kW
3.18
3.38
3.57
3.63
3.90
1350
TC
24.18
21.20
29.74
29.74
34.25
34.25
35.88
35.88
41.73
41.73
kW
3.21
3.42
3.60
3.66
3.90