Performance data – Bryant 601A User Manual
Page 11

—11—
PERFORMANCE DATA
COOLING EXTENDED PERFORMANCE TABLE
HEATING EXTENDED PERFORMANCE TABLE
-10–20
HEATING EXTENDED PERFORMANCE TABLE 30–60
*At 75°F entering dry bulb—Tennessee Valley Authority [TVA] rating conditions; all others at 80°F entering dry bulb.
See Legend and Notes on page 18.
601A018 (1.5 TONS)
Temp (F)
Air Ent
Outdoor Coil
(Edb)
Indoor Entering Air—CFM/BF
525/0.094
700/0.155
750/0.151
Indoor Entering Air—Ewb (F)
72
67
63*
62
72
67
63*
62
72
67
63*
62
85
TC
20.8
19.3
18.5
17.7
21.4
19.8
18.6
18.3
21.5
19.8
18.6
18.4
SHC
10.7
13.5
14.7
16.2
11.4
14.8
14.7
18.3
11.5
15.1
14.7
18.4
kW
1.78
1.75
1.83
1.71
1.88
1.85
1.83
1.80
1.92
1.89
1.83
1.83
95
TC
20.0
18.6
17.8
16.7
20.6
19.0
17.8
17.6
20.7
19.1
17.8
17.8
SHC
10.5
13.3
14.8
15.7
11.2
14.9
14.8
17.6
11.4
15.3
14.8
17.8
kW
1.86
1.84
1.93
1.78
1.97
1.95
1.93
1.88
2.01
1.98
1.93
1.91
105
TC
19.3
17.5
17.0
15.9
19.7
18.0
17.0
16.7
19.8
18.0
16.9
17.3
SHC
10.3
12.8
14.3
15.2
11.1
14.5
14.5
16.7
11.3
15.0
13.7
16.8
kW
1.96
1.93
1.91
1.86
2.07
2.04
2.02
1.96
2.11
2.07
2.02
2.01
115
TC
18.3
16.5
16.1
15.0
18.7
16.5
16.2
15.9
18.7
16.6
15.9
16.7
SHC
9.8
12.2
13.7
14.5
10.8
13.9
14.2
15.4
11.0
14.4
12.6
15.7
kW
2.07
2.03
2.01
1.94
2.17
2.14
2.11
2.04
2.21
2.15
2.11
2.10
601A018 (1.5 TONS)
Temp (F)
Indoor Air Cfm (std)
Air Temperature Entering Outdoor Coil (F db at 70% rh)
Ent Indoor Coil
-10
0
10
17
20
60
525
TC
2.05
2.01
4.02
3.75
5.99
5.49
7.36
6.71
8.05
7.25
kW
1.10
1.19
1.28
1.34
1.37
700
TC
2.77
2.71
5.19
4.85
7.62
6.99
9.32
8.50
10.15
9.16
kW
1.15
1.24
1.33
1.39
1.42
750
TC
2.96
2.89
5.53
5.16
8.10
7.43
9.89
9.02
10.74
9.71
kW
1.17
1.26
1.34
1.41
1.44
70
525
TC
1.52
1.51
3.46
3.23
5.40
4.95
6.75
6.16
7.42
6.68
kW
1.09
1.19
1.29
1.36
1.40
700
TC
2.04
2.02
4.48
4.18
6.90
6.34
8.61
7.85
9.45
8.51
kW
1.15
1.25
1.35
1.41
1.45
750
TC
2.21
2.19
4.77
4.47
7.34
6.74
9.14
8.34
10.05
9.03
kW
1.17
1.27
1.36
1.43
1.46
80
525
TC
0.87
0.87
2.81
2.64
4.75
4.37
6.12
5.58
6.77
6.10
kW
1.07
1.19
1.30
1.38
1.41
700
TC
1.22
1.22
3.67
3.44
6.12
5.62
7.84
7.14
8.66
7.80
kW
1.14
1.25
1.36
1.43
1.47
750
TC
1.34
1.34
3.93
3.68
6.52
5.98
8.33
7.59
9.20
8.29
kW
1.16
1.26
1.37
1.45
1.48
601A018 (1.5 TONS)
Temp (F)
Indoor Air Cfm (std)
Air Temperature Entering Outdoor Coil (F db at 70% rh)
Ent Indoor Coil
30
40
47
50
60
60
525
TC
10.34
9.06
12.93
12.93
15.02
15.02
15.72
15.72
18.40
18.40
kW
1.47
1.59
1.69
1.72
1.83
700
TC
12.93
11.34
16.11
16.11
18.00
18.00
18.80
18.80
21.39
21.39
kW
1.52
1.63
1.69
1.72
1.80
750
TC
13.73
12.04
16.91
16.91
18.90
18.90
19.60
19.60
22.38
22.18
kW
1.54
1.64
1.70
1.72
1.79
70
525
TC
9.65
8.45
12.23
12.23
14.32
14.32
15.22
15.22
18.30
18.30
kW
1.50
1.63
1.73
1.77
1.92
700
TC
12.23
10.74
15.42
15.42
17.71
17.71
18.80
18.80
21.39
21.39
kW
1.55
1.67
1.76
1.80
1.88
750
TC
12.93
11.34
16.31
16.31
18.70
18.70
19.60
19.60
22.28
22.28
kW
1.57
1.69
1.77
1.80
1.88
80
525
TC
8.96
7.86
11.54
11.54
13.53
13.53
14.42
14.42
17.51
17.51
kW
1.53
1.66
1.77
1.81
1.98
700
TC
11.44
9.95
14.62
14.62
17.01
17.01
18.00
18.00
21.29
21.29
kW
1.58
1.71
1.81
1.85
1.97
750
TC
12.14
10.64
15.42
15.42
17.90
17.90
19.00
19.00
22.28
22.28
kW
1.59
1.72
1.83
1.86
1.98