PERFORMANCE DATA (cont)
COOLING EXTENDED PERFORMANCE TABLE
HEATING EXTENDED PERFORMANCE TABLE
-10–20
HEATING EXTENDED PERFORMANCE TABLE 30–60
*At 75°F entering dry bulb—Tennessee Valley Authority [TVA] rating conditions; all others at 80°F entering dry bulb.
See Legend and Notes on page 18.
601A048 (4 TONS)
Temp (F)
Air Ent
Outdoor Coil
(Edb)
Indoor Entering Air—CFM/BF
1400
1600
1800
Indoor Entering Air—Ewb (F)
72
67
63*
62
72
67
63*
62
72
67
63*
62
85
TC
51.8
48.6
45.1
44.4
51.8
48.8
45.5
45.5
51.9
48.8
46.6
46.3
SHC
26.7
34.5
33.3
41.6
27.1
36.0
34.9
44.5
27.4
37.2
37.3
46.3
kW
4.20
4.19
4.17
4.11
4.36
4.35
4.34
4.21
4.55
4.54
4.54
4.34
95
TC
50.8
46.7
43.0
42.1
50.8
47.0
43.4
43.5
50.9
47.0
45.5
44.8
SHC
26.5
33.8
32.2
40.0
27.0
35.4
33.8
43.5
27.4
36.8
36.4
44.8
kW
4.58
4.57
4.55
4.45
4.75
4.74
4.73
4.59
4.95
4.93
4.89
4.71
105
TC
49.0
44.7
40.9
40.3
49.1
44.7
41.3
41.5
49.2
45.0
43.3
42.7
SHC
25.9
33.1
31.2
39.1
26.5
34.4
32.9
41.5
27.0
36.2
36.4
42.7
kW
5.00
5.02
4.92
4.81
5.16
5.15
5.11
4.94
5.35
5.31
5.27
5.13
115
TC
47.1
42.1
38.8
37.3
47.3
42.4
41.6
39.9
47.4
42.8
42.5
40.7
SHC
25.2
31.7
32.2
37.3
25.7
33.5
35.7
39.9
26.3
35.6
37.7
40.7
kW
5.47
5.41
5.33
5.29
5.61
5.57
5.41
5.33
5.80
5.75
5.56
5.54
601A048 (4 TONS)
Temp (F)
Indoor Air Cfm (std)
Air Temperature Entering Outdoor Coil (F db at 70% rh)
Ent Indoor Coil
-10
0
10
17
20
60
1400
TC
16.34
13.83
20.69
17.60
25.04
23.01
28.43
25.91
30.26
27.27
kW
3.22
3.34
3.44
3.52
3.57
1600
TC
16.63
14.12
20.98
17.89
25.43
23.30
28.81
26.30
30.55
27.56
kW
3.27
3.36
3.47
3.55
3.59
1800
TC
16.82
14.31
21.27
18.08
25.72
23.59
29.10
26.59
30.94
27.94
kW
3.31
3.41
3.51
3.59
3.63
70
1400
TC
15.57
13.25
20.02
17.02
24.46
22.43
27.85
25.43
29.49
26.59
kW
3.45
3.57
3.68
3.78
3.83
1600
TC
15.86
13.54
20.31
17.31
24.85
22.82
28.23
25.72
29.97
27.07
kW
3.50
3.61
3.71
3.80
3.85
1800
TC
16.15
13.73
20.69
17.60
25.14
23.11
28.52
26.01
30.36
27.36
kW
3.55
3.65
3.74
3.83
3.88
80
1400
TC
14.70
12.47
19.24
16.34
23.69
21.76
27.17
24.75
28.81
26.01
kW
3.68
3.82
3.95
4.05
4.11
1600
TC
14.99
12.76
19.53
16.63
24.08
22.14
27.56
25.14
29.20
26.30
kW
3.73
3.85
3.97
4.07
4.12
1800
TC
15.28
13.05
19.82
16.92
24.46
22.43
27.94
25.43
29.59
26.69
kW
3.78
3.89
4.00
4.10
4.14
601A048 (4 TONS)
Temp (F)
Indoor Air Cfm (std)
Air Temperature Entering Outdoor Coil (F db at 70% rh)
Ent Indoor Coil
30
40
47
50
60
60
1400
TC
36.16
31.71
42.54
42.54
47.67
47.67
48.25
48.25
53.95
53.95
kW
3.72
3.90
4.03
3.99
4.11
1600
TC
36.55
32.00
43.03
43.03
47.77
47.77
49.31
49.31
54.53
54.53
kW
3.72
3.89
4.01
4.03
4.15
1800
TC
36.94
32.39
43.03
43.03
47.96
47.96
49.41
49.41
55.79
55.79
kW
3.75
3.89
4.00
4.08
4.24
70
1400
TC
35.10
30.75
41.67
41.67
47.09
47.09
48.15
4815
53.66
53.66
kW
3.98
4.17
4.36
4.41
4.46
1600
TC
35.87
31.42
42.16
42.16
47.28
47.28
49.02
49.02
54.34
54.34
kW
3.99
4.17
4.31
4.35
4.52
1800
TC
36.26
31.71
42.54
42.54
47.67
47.67
49.12
48.83
54.63
54.63
kW
4.01
4.18
4.31
4.45
4.46
80
1400
TC
34.33
30.07
40.80
40.80
46.12
46.12
47.86
47.86
53.18
53.18
kW
4.28
4.49
4.69
4.75
4.97
1600
TC
34.71
30.46
41.29
41.29
46.61
46.61
48.35
48.35
54.24
54.24
kW
4.28
4.47
4.66
4.70
4.91
1800
TC
35.10
30.75
41.67
41.67
47.09
47.09
48.44
48.44
54.44
54.44
kW
4.29
4.47
4.64
4.67
4.83