Instruction Manual – Model CF1400 Oil Burner

Figure 1 - Min. Combustion chamber dimensions

1405

A

L

Figure 2 - Air tube mounting dimensions

E

T

D

1404

G

1

E Insertion depth
G Air tube to inside of chamber

– 0.25" ± 0.125"

T Air tube length
D Tube diameter

Install the burner with a 2° pitch as shown.

Air tube

length

(Dimension T)

A.T.C. Codes

(A.T.C. = Air Tube Combination)

Tube A

(Dim. D = 5½")

Tube B

(Dim. D = 5¾")

6.75"

CF 66 KD

CF 66 KE

10.25"

CF 102 KD

CF 102 KE

13.75"

CF 136 KD

CF 136 KE

17.75"

CF 176 KD

CF 176 KE

Table 2 - Air tube capacity vs. firebox pressure

Firebox

pressure

(In. w.c.)

Tube A

Tube B

10% turndown No reserve air 10% turndown

0.0

11.0 GPH

13.6 GPH

12.2 GPH

0.2

10.5 GPH

13.1 GPH

11.7 GPH

0.4

10.1 GPH

12.5 GPH

11.2 GPH

0.6

9.6 GPH

12.0 GPH

10.8 GPH

0.8

9.2 GPH

11.4 GPH

10.3 GPH

1.0

8.7 GPH

10.9 GPH

9.8 GPH

Note: 10% turndown indicates sufficient reserve air to reduce the CO

2

in the

flue to 90% of its value.

Note: The above ratings may vary 5% due to variations in actual job conditions.

Verify firing rate

• Refer to appliance manufacturer’s instructions (if avail-

able) for firing rate and nozzle selection. Otherwise, the
maximum recommended firing rate for the burner depends
on the length of the firing chamber and the distance from
the burner center to the chamber floor. Verify that the cham-
ber dimensions are at least as large as the minimum values
given in

Figure 1

. If the appliance dimensions are smaller

than recommended, reduce the firing rate accordingly.

Verify air tube

• The information in this section may be disregarded if the

air tube is supplied by the appliance manufacturer.

• Two tube arrangements are available –

Tube

A

— 4.0 to 11.0 GPH per

Table 2

Tube

B

— 7.0 to 13.6 GPH per

Table 2

• Maximum firing capacity depends on the firebox pressure.

Use

Table 2

to verify the correct air tube type for the firing

rate required. Use Tube

B

only when Tube

A

cannot pro-

vide the firing rate required.

• See

Figure 2

to verify the correct air tube length and air

tube combination code.

Firing rate

Minimum dimensions

(refractory-lined)

(wet-base boilers)

A

L

A

L

0 to 5 gph

7.0"

25.0"

7.0"

25.0"

5 to 10 gph

8.0"

35.0"

8.0"

40.0"