Bryant COMMERCIAL AIR COOLED CONDENSING UNITS 576b User Manual

Page 7

background image

7

Table 4 — Electrical Data

LEGEND

NOTES:
1. In compliance with NEC requirements for multimotor and combina-

tion load equipment (refer to NEC Articles 430 and 440), the over-
current protective device for the unit shall be fuse or HACR breaker.
The Canadian units may be fuse or circuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is
greater than 2%.
Use the following formula to determine the percent
of voltage imbalance.

% of Voltage Imbalance =

EXAMPLE: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.

Determine percent of voltage imbalance:

This amount of phase imbalance is satisfactory as it is below the maxi-
mum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.
3. The 575-v units are CSA only.

4. The 380-v units are not UL or CSA listed.

UNIT

NOMINAL VOLTAGE

(V-Ph-Hz)

VOLTAGE RANGE

COMPRESSOR

OFM

POWER SUPPLY

Min

Max

RLA

LRA

FLA

MCA

MOCP

569C072

208/230-3-60

187

254

21.8

158

1.9

30.1

40

460-3-60

414

508

10.0

79

1.0

13.5

20

575-3-60

518

632

9.0

65

1.9

14.1

20

569C090

208/230-3-60

187

254

28.8

195

3.8

39.8

50

460-3-60

414

508

14.7

95

1.9

20.3

25

575-3-60

518

632

10.8

80

1.9

15.4

20

569C120

208/230-3-60

187

254

37.8

239

3.1

51.1

70

460-3-60

414

508

17.2

125

1.4

23.4

30

575-3-60

518

632

14.3

90

1.4

19.8

25

576B090

208/230-3-60

187

254

31.5

160

3.1

42.5

50

380-3-60

342

418

19.0

75

2.2

26.0

35

460-3-60

414

508

15.7

80

1.4

21.0

25

575-3-60

518

632

12.6

64

1.4

17.2

20

576B102

208/230-3-60

187

254

39.7

198

3.1

52.7

70

380-3-60

342

418

24.0

93

2.2

32.2

40

460-3-60

414

508

19.9

99

1.4

26.3

35

575-3-60

518

632

15.9

79

1.4

21.3

25

576B120

208/230-3-60

187

254

39.7

198

3.1

52.7

70

380-3-60

342

418

24.0

93

2.2

32.2

40

460-3-60

414

508

19.9

99

1.4

26.3

35

575-3-60

518

632

15.9

79

1.4

21.3

25

CSA

Canadian Standards Association

FLA

Full Load Amps

HACR —

Heating, Air Conditioning and Refrigeration

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP —

Maximum Overcurrent Protection

NEC

National Electrical Code

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

UL

Underwriters’ Laboratories

100 x

max voltage deviation from average voltage

average

voltage

Average Voltage

=

452 + 464 + 455

3

=

1371

3

=

457

% Voltage Imbalance

=

100 x

7

457

=

1.53%