beautypg.com

Bryant COMMERCIAL AIR COOLED CONDENSING UNITS 576b User Manual

Page 10

background image

10

SERVICE

I. CLEANING

Inspect unit interior at the beginning of each cooling season
and as operating conditions require.

A. Condenser Coil

Inspect coil monthly. Clean condenser coil annually, or as
required by location and outdoor-air conditions.

Clean coil as follows:

1. Turn off unit power and tag disconnect.

2. Remove and save top panel screws on condensing

unit.

3. Remove condenser coil corner post. See Fig. 8. To hold

top panel open, place coil corner post between top
panel and side panel. See Fig. 9.

4. Remove bracket holding coil sections together at

return end of condenser coil. Carefully separate the
outer coil section 3 to 4 in. from the inner coil section.
See Fig. 10.

5. Use a water hose or other suitable equipment to flush

down between the 2 coil sections to remove dirt and
debris. Clean the outer surfaces with a stiff brush in
the normal manner.

6. Reposition the outer coil section, attach the bracket

removed in Step 4, and remove the coil corner post
from between the top panel and side panel. Secure
the sections together. Install the coil corner post and
replace all screws (removed in Step 2).

II. LUBRICATION

A. Compressors

Each compressor is charged with the correct amount of oil at
the factory. Refer to the Oil Charge section on page 9 for
additional information.

B. Fan Motor Bearings

Fan motor bearings are of the permanently lubricated type.
No further lubrication is required.

III. CONDENSER-FAN ADJUSTMENT (Fig. 11)

1. Shut off unit power supply, and tag disconnect.

2. Remove condenser-fan assembly (grille, motor, motor

cover, and fan).

3. Loosen fan hub setscrews.

4. Adjust fan height as shown in Fig. 11.

5. Tighten set screws.

6. Replace condenser-fan assembly.

WARNING: When servicing unit, shut off all elec-

trical power to unit to avoid shock hazard or injury
from rotating parts.

Fig. 8 — Cleaning Condenser Coil

Fig. 9 — Propping Up Top Panel

Fig. 10 — Separating Coil Sections

NOTE: Fan height adjustments are as follows:

Fig. 11 — Outdoor (Condenser) Fan Adjustment

UNIT

in.

mm

569C072

4.50

114

All Units

(except 569C072)

6.42

163