beautypg.com

Bryant 345MAV User Manual

Page 7

background image

III.

DOWNFLOW APPLICATIONS

A downflow furnace application is where furnace blower is located
above combustion and controls section of furnace, and conditioned
air is discharged downwards.

A.

Condensate Trap Location

The condensate trap must be removed from the factory-installed
blower shelf location and relocated in selected application location
as shown in Fig. 2, 7, or 8.

To relocate condensate trap from the blower shelf to desired
location, perform the following:

1. Remove 3 tubes connected to condensate trap.

2. Remove trap from blower shelf by gently pushing tabs

inward and rotating trap.

3. Remove casing hole filler cap from casing hole. (See Fig. 2,

7, or 8.)

4. Install casing hole filler cap into blower shelf hole where

trap was removed.

5. Install condensate trap into desired casing hole by inserting

tube connection stubs through casing hole and rotating until
tabs snap into locking position.

B.

Condensate Trap Tubing

NOTE:

See Fig. 7 or 8 or tube routing label on main furnace door

to check for proper connections.

1. Collector Box Drain Tube

a. Remove factory-installed plug from LOWER collector

box drain tube (blue and white striped label).

b. Install removed clamp and plug into UPPER collector

box drain tube (blue label) which was connected to
condensate trap.

c. Connect LOWER collector box drain connection to

condensate trap.

(1.) Condensate Trap Located on Left Side of Casing

(a.) Connect LOWER collector box drain tube

(blue and white striped label) to condensate
trap. Tube does not need to be cut.

(b.) Clamp tube to prevent any condensate leakage.

(2.) Condensate Trap Located on Right Side of Casing

(a.) Install drain tube coupling (factory-supplied in

loose parts bag) into collector box drain tube
(blue and white striped label) which was pre-
viously plugged.

(b.) Connect larger diameter drain tube (factory-

supplied in loose parts bag) to drain tube
coupling, extending collector box drain tube
for connection to condensate trap.

(c.) Route extended collector box drain tube be-

tween gas valve and inlet housing as shown in
Fig. 8.

(d.) Determine appropriate length and cut.

(e.) Connect to condensate trap.

(f.) Clamp tube to prevent any condensate leakage.

2. Inducer Housing Drain Tube

a. Remove factory-installed cap and clamp from LOWER

inducer housing drain connection.

b. Remove and discard UPPER (molded) inducer housing

drain tube which was previously connected to conden-
sate trap.

c. Install cap and clamp on UPPER inducer housing drain

connection where molded drain tube was removed.

Fig. 7—Downflow Tube Configuration

(Left-Hand Trap Installation)

A94165

PLUG

COLLECTOR BOX

TUBE (GREEN)

COLLECTOR BOX

TUBE (PINK)

COLLECTOR BOX

DRAIN TUBE (BLUE

& WHITE STRIPED)

COLLECTOR BOX

EXTENSION TUBE

CONDENSATE

TRAP

INDUCER HOUSING

DRAIN TUBE (VIOLET)

COLLECTOR BOX

EXTENSION TUBE

CAP

COLLECTOR BOX

DRAIN TUBE (BLUE)

Fig. 8—Downflow Tube Configuration

(Right-Hand Trap Installation)

A94166

PLUG

COLLECTOR BOX
TUBE (GREEN)

COLLECTOR BOX
TUBE (PINK)

COLLECTOR BOX
DRAIN TUBE (BLUE
& WHITE STRIPED)

COLLECTOR BOX
EXTENSION
DRAIN TUBE

CONDENSATE
TRAP

INDUCER HOUSING
DRAIN TUBE
(VIOLET)

COLLECTOR BOX
EXTENSION TUBE

DRAIN TUBE
COUPLING

COLLECTOR BOX
DRAIN TUBE (BLUE)

CAP

COLLECTOR BOX
EXTENSION TUBE

—7—