beautypg.com

Bryant 345MAV User Manual

Page 32

background image

5. Remove funnel and tube from inducer housing and replace

drain connection cap and clamp.

III.

PURGE GAS LINES

If not previously done, purge lines after all connections have been
made and check for leaks.

WARNING:

Never purge a gas line into a combustion

chamber. Never use matches, candles, flame, or other
sources of ignition for purpose of checking leakage. Use
a soap-and-water solution to check for leakage. Failure to
follow this warning could result in fire, explosion, per-
sonal injury, or death.

IV.

ADJUSTMENTS

A.

Set Gas Input Rate

Furnace gas input rate on rating plate is for installations at altitudes
up to 2000 ft. Furnace input rate must be within

±

2 percent of input

on furnace rating plate.

1. Determine natural gas orifice size and manifold pressure for

correct input.
a. Obtain average yearly heat value (at installed altitude)

from local gas supplier.

b. Obtain average yearly specific gravity from local gas

supplier.

c. Verify furnace model. Table 7 can only be used for

model 345MAV furnaces.

d. Find installation altitude in Table 7.

NOTE:

For Canada altitudes of 2000 to 4500 ft, use U.S.A.

altitudes of 5001 to 6000 ft in Table 7.

e. Find closest natural gas heat value and specific gravity

on Table 7.

f. Follow heat value and specific gravity lines to point of

intersection to find orifice size and manifold pressure
settings for proper operation.

EXAMPLE: (0—2000 altitude)
Heating value = 1050 Btu/cu ft
Specific gravity = 0.62
Therefore: Orifice No. 45

Manifold pressure 3.6-in. wc

* Furnace is shipped with No. 45 orifices. In this example
all main burner orifices are the correct size and do not need
to be changed to obtain the proper input rate.

Check and verify burner orifice size in furnace. NEVER ASSUME
ORIFICE SIZE; ALWAYS CHECK AND VERIFY.

2. Adjust manifold pressure to obtain input rate.

NOTE:

Manifold pressure must always be measured with burner

enclosure front REMOVED. Gas meter must always be clocked
with burner enclosure front INSTALLED.

a. Remove burner enclosure front.

b. Remove cap that conceals adjustment screw for gas

valve regulator. (See Fig. 40.)

c. Turn adjusting screw, counterclockwise (out) to decrease

manifold pressure or clockwise (in) to increase manifold
pressure.

NOTE:

This furnace has been approved for a manifold pressure

of 3.2 in. wc to 3.8 in. wc when installed at altitudes up to 2000 ft.
For altitudes above 2000 ft, the manifold pressure can be adjusted
from 2.0 in. wc to 3.8 in. wc.

Fig. 38—Inducer Housing Drain Tube

A94208

Fig. 39—Filling Condensate Trap

A94209

—32—