beautypg.com

Bryant Gas Heating/Electric Cooling Units 581B User Manual

Page 10

background image

3. Voltage to compressor terminals during operation must

be within voltage range indicated on unit nameplate (also
see Tables 3A and 3B). On 3-phase units, voltages be-
tween phases must be balanced within 2% and the cur-
rent within 10%. Use the formula shown in Tables 3A
and 3B, Note 2, to determine the percent voltage im-
balance. Operation on improper line voltage or exces-
sive phase imbalance constitutes abuse and may cause
damage to electrical components. Such operation would
invalidate any applicable warranty.

4. Insulate low-voltage wires for highest voltage con-

tained within conduit when low-voltage control wires are
run in same conduit as high-voltage wires.

5. Do not damage internal components when drilling through

any panel to mount electrical hardware, conduit, etc.

NOTE:

If accessory thru-the-bottom connections and roof curbs

are used, refer the Thru-the-Bottom Installation Instruc-
tions for information on power wiring.

Fig. 13 — Power Wiring Connections

LEGEND

AHA — Adjustable Heat Anticipator

TC

Thermostat-Cooling

CC

Cooling Compensator

TH

Thermostat-Heating

RC

24-v Cooling

Field Wiring

RH

24-v Heating

Factory Wiring

NOTE: Connect Y2 when unit is equipped with an integrated
economizer.

Fig. 14 — Low-Voltage Connections With or

Without Economizer or Two-Position Damper

LOW VOLTAGE
CONNECTIONS
(SCREW TERMINALS)

INTEGRATED GAS UNIT
CONTROLLER (IGC)

HOLE IN END PANEL (HIDDEN)

RACEWAY

Fig. 15 — Field-Control Wiring Raceway

LEGEND

C

Contactor

COMP — Compressor
EQUIP — Equipment
GND

Ground

IFC

Indoor (Evaporator) Fan

Contactor

NEC

National Electrical Code

—10—