beautypg.com

577d -- -- a – Bryant EVOLUTION 577D----A User Manual

Page 29

background image

29

Table 6 – Heating Input

s

HEATING INPUT (BTU/HR)*

NUMBER OF

GAS SUPPLY PRESSURE (IN. W.C.)

MANIFOLD PRESSURE (IN. W.C.)

NUMBER OF

ORIFICES

Natural

Natural

High Stage

Low Stage

ORIFICES

Min

Max

High Stage

Low Stage

40,000

26,000

2

4.0

13.0

3.2∼ 3.8

1.4 ∼ 2.0

60,000

39,000

3

4.0

13.0

3.2∼ 3.8

1.4 ∼ 2.0

90,000

58,500

3

4.0

13.0

3.2∼ 3.8

1.4 ∼ 2.0

115,000

75,000

3

4.0

13.0

3.2∼ 3.8

1.4 ∼ 2.0

130,000

84,500

3

4.0

13.0

3.2∼ 3.8

1.4 ∼ 2.0

*Cubic ft of natural gas per hour for gas pressures of .5 psig (14 IN. W.C.) or less and a pressure drop of .5 IN. W.C. (based on a .60 specific gravity gas). Ref:

Table 6.2 (b) NPFA 54 / ANSI Z223.1---2009.

Table 7 – ECM Wet Coil Pressure Drop (IN. W.C.)

UNIT

SIZE

STANDARD CFM (SCFM)

600

700

800

900

1000

1100

1200

1300

1400

1500

1600

1700

1800

1900

2000

2100

24

0.005

0.007

0.010

0.012

0.015

30

0.007

0.010

0.012

0.015

0.018

0.021

0.024

36

0.019

0.023

0.027

0.032

0.037

0.042

0.047

42

0.014

0.017

0.020

0.024

0.027

0.031

0.035

0.039

0.043

48

0.027

0.032

0.036

0.041

0.046

0.052

0.057

0.063

0.068

60

0.029

0.032

0.036

0.040

0.045

0.049

0.053

Table 8 – Filter Pressure Drop Table (IN. W.C.)

FILTER SIZE

in. (mm)

CFM

500

600

700

800

900

1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300

20X20X1

(508x508x25) 0.05

0.07

0.08

0.1

0.12

0.13

0.14

0.15

24X30X1

(610x762x25)

0.05

0.6

0.07

0.07

0.08

0.09

0.1

24X36X1

(610x914x25)

0.06

0.07

0.07

0.08

0.09

0.09

0.10

0.11

0.12

0.13

0.14

0.14

IMPORTANT:

When evaluating the refrigerant charge, an

indicated adjustment to the specified factory charge must always be
very minimal. If a substantial adjustment is indicated, an abnormal
condition exists somewhere in the cooling system, such as
insufficient airflow across either coil or both coils.
REFRIGERANT CHARGE
The amount of refrigerant charge is listed on the unit rating plate

and/or the physical data table. Refer to the Refrigeration Service
Techniques Manual, Refrigerants Section.
NO CHARGE
Check for leak. Use standard evacuating techniques. After

evacuating system, weigh in the specified amount of refrigerant

(refer to system rating plate).
LOW CHARGE COOLING
Use Cooling Charging Chart (Fig. 23). Vary refrigerant until the
conditions of the chart are met. Note that charging charts are

different from type normally used. Charts are based on charging
the units to correct subcooling for the various operating conditions.

Accurate pressure gauge and temperature sensing devices are

required. Connect the pressure gauge to the service port on the
suction line. Mount the temperature sensing device on the suction

line and insulate it so that the outdoor ambient does not affect the
reading. Indoor air CFM must be within the normal operating

range of the unit.

TO USE COOLING CHARGING CHARTS
Take the liquid line temperature and read the manifold pressure

gauges.
Refer to the chart to determine what the liquid line temperature

should be.
NOTE:

If the problem causing the inaccurate readings is a

refrigerant leak, refer to Check for Refrigerant Leaks section.
NON--COMMUNICATING

EMERGENCY

COOLING

/

HEATING MODE: 4--WIRE THERMOSTAT
This mode of operation is provided only in the case where the UI
has failed or is otherwise unavailable. If communications cannot be

established with the UI, the Evolution furnace board will enable
the standard thermostat input terminals

to allow simple

thermostatic control of the 577D----A unit.
For control with a standard thermostat, disconnect the ABCD

connectors from both control boards and using No. 18 AWG

color--coded, insulated type 90°C minimum or equivalent wire,

make the connections between the standard thermostat, the furnace

board, and the HP/AC board per Fig. 22. Recommend the use of
interconnecting wire with 105C, 600V, 2/64” insulation.
The Evolution control will respond to cooling and heating

demands with the maximum safe airflow based on gas furnace
output and unit cooling capacity.

577D

--

--

A