beautypg.com

Warning, Caution – Bryant EVOLUTION 577D----A User Manual

Page 10

background image

10

2. Avoid abrupt duct size increases and reductions. Abrupt

change in duct size adversely affects air performance.

IMPORTANT: Use flexible connectors between ductwork and
unit to prevent transmission of vibration. Use suitable gaskets to
ensure weather tight and airtight seal. When electric heat is
installed, use fireproof canvas (or similar heat resistant material)
connector between ductwork and unit discharge connection. If
flexible duct is used, insert a sheet metal sleeve inside duct. Heat
resistant duct connector (or sheet metal sleeve) must extend 24--in.
(610 mm) from electric heater element.

3. Size ductwork for max possible air flow (See Table 1).
4. Seal, insulate, and weatherproof all external ductwork. Seal,

insulate and cover with a vapor barrier all ductwork passing
through conditioned spaces. Follow latest Sheet Metal and

Air Conditioning

Contractors

National Association

(SMACNA) and Air Conditioning Contractors Association

(ACCA) minimum installation standards for residential
heating and air conditioning systems.

5. Secure all ducts to building structure. Flash, weatherproof,

and vibration--isolate duct openings in wall or roof
according to good construction practices.

6. Read unit rating plate for any required clearances around

ductwork.

Configuring Units for Downflow (Vertical) Discharge

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal

injury or death.
Before installing or servicing system, always turn off main

power to system and install lockout tag. There may be

more than one disconnect switch.

!

WARNING

1. Open all electrical disconnects before starting any service

work.

2. Remove horizontal (metal) duct covers to access vertical

(downflow) discharge duct knockouts in unit basepan. (See

Fig. 8.)

PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
Collect ALL screws that were removed. Do not leave screws

on rooftop as permanent damage to the roof may occur.

CAUTION

!

To remove downflow return and supply knockout covers, break

front and right side connecting tabs with a screwdriver and
hammer. Push cover down to break rear and left side tabs.
NOTE: These panels are held in place with tabs similar to an
electrical knockout. Reinstall horizontal duct covers (see Fig. 8)
shipped on unit from factory. Insure openings are air and
watertight.
The design and installation of the duct system must be in

accordance with the standards of the NFPA for installation of

nonresidence--type air conditioning and ventilating systems, NFPA
90A or residence--type, NFPA 90B; and/or local codes and

ordinances.
Adhere to the following criteria when selecting, sizing, and

installing the duct system:

1. Units are shipped for horizontal duct installation (by

removing duct covers).

Horizontal Duct Covers

A09076

Basepan
Downflow
(Vertical)
Supply
Knockout

Basepan
Downflow
(Vertical)
Return
Knockout

A09077

Fig. 8 -- Supply and Return Duct Opening

2. Select and size ductwork, supply--air registers, and

return--air grilles according to American Society of Heating,
Refrigeration and Air Conditioning Engineers (ASHRAE)

recommendations.

3. Use flexible transition between rigid ductwork and unit to

prevent transmission of vibration. The transition may be
screwed or bolted to duct flanges. Use suitable gaskets to
ensure weather--tight and airtight seal.

4. All units must have field--supplied filters or accessory filter

rack installed in the return--air side of the unit.

Recommended sizes for filters are shown in Table 1.

5. Size all ductwork for maximum required airflow (either

heating or cooling) for unit being installed. Avoid abrupt

duct size increases or decreases or performance may be
affected.

6. Adequately insulate and weatherproof all ductwork located

outdoors. Insulate ducts passing through unconditioned

space, and use vapor barrier in accordance with latest issue
of Sheet Metal and Air Conditioning Contractors National
Association (SMACNA) and Air Conditioning Contractors

of America (ACCA) minimum installation standards for
heating and air conditioning systems. Secure all ducts to

building structure.

7. Flash, weatherproof, and vibration isolate all openings in

building structure in accordance with local codes and good

building practices.

Provide for Condensate Disposal

NOTE: Ensure that condensate--water disposal methods comply
with local codes, restrictions, and practices.
The units dispose of condensate through a 3/4 --in. NPT female

fitting that exits on the compressor end of the unit. Condensate

water can be drained directly onto the roof in rooftop installations
(where permitted) or onto a gravel apron in ground level

installations. Install a field--supplied condensate trap at end of
condensate connection to ensure proper drainage. Make sure that

577D

--

--

A