a. 129 sec. to complete one revolution

b. 3600/129 = 27.9

c. 27.9 x 2 = 55.8 ft

3

of gas flow/hr.

d. 55.8 x 1050 = 58,590 Btuh input.

In this example, the nominal input rate for low stage is 58,500

Btu/hr, so the low stage manifold pressure is correctly set.
If the measured low stage rate is too low, increase the manifold
pressure to increase rate. If the measured low stage rate is too high,

decrease the manifold pressure to decrease rate.
NOTE: Double--check that UI is running on low stage gas heat
while clocking the low stage firing rate.

4. Verify proper low stage gas heat temperature rise.

a. Furnace must operate within rise range listed on rating

plate.

b. Select ”COMFORT” or ”EFFICIENCY” mode on UI.

”COMFORT” mode will provide a warmer supply air
temperature, while ”EFFICIENCY” will provide lower
gas consumption.

c. Make sure access panel is re--installed on the unit.

d. Measure supply and return temperatures as close to the

unit as possible. Subtract the return temperature from
the supply temperature to determine rise. Rise should

fall within the range specified on the rating plate.

5. Adjust manifold pressure to obtain high stage input rate

(See Fig. 19).

a. Set unit to run for 20 minutes in high--stage gas heat

operation using the ”INSTALLER CHECKOUT” menu

on the UI.

b. Remove regulator adjustment cap from high stage gas

valve pressure regulator (See Fig. 19) and turn

high--stage adjusting screw (3/16 or smaller flat--tipped
screwdriver) counterclockwise (out) to decrease rate and

clockwise (in) to increase input rate.

NOTE: DO NOT set high stage manifold pressure less than 3.2
IN. W.C. or more than 3.8 IN. W.C. for natural gas. If manifold
pressure is outside this range, change main burner orifices.

c. Re--install high stage regulator adjustment cap.

d. Leave manometer connected.

6. Verify natural gas high stage input rate.

a. Turn off all other gas appliances and pilots served by

the gas meter.

b. If unit is not running, set unit to run for 20 minutes in

high stage gas heat operation using the ”INSTALLER
CHECKOUT” menu on the UI.

c. Record number of seconds for gas meter to complete 1

revolution.

d. Divide number of seconds in step c. into 3600 (number

of seconds in 1 hour).

e. Multiply result of step d. by the number of cubic feet

shown for one revolution of test dial to obtain cubic feet

of gas flow per hour.

f. Multiply result of step f. by Btu heating value of the gas

to obtain total measured input shown in Table 6.
(Consult the local gas supplier if the heating value of
gas is not known).

EXAMPLE: Assume a 90,000 high stage input unit is being
installed. Assume that the size of the dial is 2 cubic ft., one

revolution takes 84 sec., and the heating value of the gas is 1025

Btu/ft3. Proceed as follows:

a. 84 sec. to complete one revolution

b. 3600/84 = 42.9

c. 42.9 x 2 = 85.8 ft3 of gas flow/hr.

d. 85.8 x 1050 = 90,090 Btuh input.

In this example, the nominal input rate for high stage is 90,000
Btu/hr, so the high stage manifold pressure is correctly set.
If the measured high stage rate is too low, increase the manifold
pressure to increase rate. If the measured high stage rate is too

high, decrease the manifold pressure to decrease rate.
NOTE: Double--check that User Interface is running on high stage
gas heat while clocking the low stage firing rate.

7. Verify proper high stage gas heat temperature rise.

a. Furnace must operate within rise range listed on rating

plate.

b. Make sure access panel is re--installed on the unit.

c. Measure supply and return temperatures as close to the

unit as possible. Subtract the return temperature from

the supply temperature to determine rise. Rise should
fall within the range specified on the rating plate.

NOTE: If the temperature rise is outside the rating plate range,
first check:

a. Gas input for low and high stage gas heat operation.

b. Derate for altitude, if applicable.

c. Return and supply ducts for excessive restrictions

causing static pressures in excess of .5 IN. W.C.

d. Make sure model plug is installed.

8. Final Check

a. Turn off gas to unit

b. Remove manometer from pressure tap.

c. Replace pipe plug on manifold (See Fig. 20).

d. Turn on gas to unit.

e. Check for leaks.

CHECK GAS INPUT (PROPANE GAS)
Refer to propane kit installation instructions for properly checking

gas input.
NOTE: For installations below 2,000 ft (610 m), refer to the unit
rating plate for proper propane conversion kit. For installations
above 2,000 ft (610 m), contact your distributor for proper propane
conversion kit.
CHECK BURNER FLAME
With control access panel removed (See Fig. 24), observe the unit
heating operation. Watch the burner flames to see if they are light

blue and soft in appearance, and that the flames are approximately
the same for each burner. Propane will have blue flame (See Fig.

21). Refer to the Maintenance section for information on burner