beautypg.com

Maintenance – American Water Heater BCG3 User Manual

Page 28

background image

28

figure 26.

if the Temperature-Pressure Relief Valve on the water heater

weeps or discharges periodically, this may be due to thermal

expansion.
NoTe: excessive water pressure is the most common cause of

Temperature-Pressure Relief Valve leakage. excessive water

system pressure is most often caused by "thermal expansion"

in a "closed system." See Closed Water Systems and Thermal

expansion on page 12. The Temperature-Pressure Relief Valve

is not intended for the constant relief of thermal expansion.
Temperature-Pressure Relief Valve leakage due to pressure

build up in a closed system that does not have a thermal

expansion tank installed is not covered under the limited

warranty. Thermal expansion tanks must be installed on all

closed water systems.
Do NoT PluG THE TEMPERaTuRE-PREssuRE RElIEF

VALVe oPeNiNG. THiS CAN CAuSe PRoPeRTY DAmAGe,

SeRiouS iNJuRY oR DeATH.

Explosion Hazard

Temperature-Pressure Relief Valve

must comply with ANSI Z21.22-

CSA 4.4 and ASME code.

Properly sized temperature-

pressure relief valve must be

installed in opening provided.

Can result in overheating and

excessive tank pressure.

Can cause serious injury or death.

hot water odor

on occasion, hot water may develop a strong odor. if this occurs

drain the heater completely, flush thoroughly, and refill. if the

problem persists, chlorination of the heater and replacement

of magnesium anodes with aluminum anodes may correct the

condition.

occasionally water softener companies recommend removal of

heater anodes for odor reasons.

unauthorized removal of the anode(s) will void the warranty. for

further information contact your dealer.

Venting system

examine the venting system every six months for obstructions

and/or deterioration of the vent piping.
Remove all soot or other obstructions from chimney which will

retard free draft.

remote storage tank temperature control

The water temperature in the remote storage tank (if used) is

controlled by the storage tank temperature control. The sensing

element is mounted in the hot water storage tank, see Water

Piping Diagram section.
A change in water temperature in the storage tank lower than

the tank temperature control setting will cause the sensor to

activate the circulating pump. The pump then circulates the

water through the heater where the thermostat senses the drop

in water temperature and activates main burner operation of the

appliance.
if the storage tank temperature control is out of calibration, replace

with new control.
SHouLD oVeRHeATiNG oCCuR oR THe GAS SuPPLY fAiL

To SHuT off, TuRN off THe mANuAL GAS CoNTRoL VALVe

To THe APPLiANCe.

temperature-pressure relief ValVe test

Burn hazard.

Hot water discharge.

Keep clear of Temperature-

Pressure Relief Valve

discharge outlet.

it is recommended that the Temperature-Pressure Relief Valve

should be checked to ensure that it is in operating condition every

6 months.
When checking the Temperature-Pressure Relief Valve operation,

make sure that (1) no one is in front of or around the outlet of the

Temperature-Pressure Relief Valve discharge line, and (2) that

the water discharge will not cause any property damage, as the

water may be extremely hot. use care when operating valve as

the valve may be hot.
To check the relief valve, lift the lever at the end of the valve

several times, see figure 26. The valve should seat properly and

operate freely.
if after manually operating the valve, it fails to completely reset and

continues to release water, immediately close the cold water inlet

to the water heater and drain the water heater, see Draining And

flushing on page 28. Replace the Temperature-Pressure Relief
Valve with a properly rated/sized new one, see Temperature-

Pressure Relief Valve on pages 12-13 for instructions on

replacement.

maintenance