gas piping

Contact your local gas service company to ensure that adequate gas

service is available and to review applicable installation codes for

your area.
Size the main gas line in accordance with Table 9. The figures shown

are for straight lengths of pipe at 0.5 in. W.C. pressure drop, which is

considered normal for low pressure systems. Note: fittings such as

elbows, tees and line regulators will add to the pipe pressure drop. Also

refer to the latest version of the National fuel Gas Code.
Schedule 40 metallic Pipe is the preferred material for the gas line of

this water heater. it is imperative to follow the sizing recommendations in

the latest version of the National fuel Gas Code if Corrugated Stainless

Steel Tubing (CSST) is used as the gas line for this water heater.
THE HEaTER Is NoT INTENDED FoR oPERaTIoN aT HIGHER

THAN 14.0” W.C.- NATuRAL GAS, (1/2 PouND PeR SquARe iNCH

GAGe) SuPPLY GAS PReSSuRe. eXPoSuRe To HiGHeR SuPPLY

PReSSuRe mAY CAuSe DAmAGe To THe GAS VALVe WHiCH

CouLD ReSuLT iN fiRe oR eXPLoSioN. if oVeRPReSSuRe HAS

oCCuRReD SuCH AS THRouGH imPRoPeR TeSTiNG of GAS

LiNeS oR emeRGeNCY mALfuNCTioN of THe SuPPLY SYSTem,

THe GAS VALVe muST Be CHeCKeD foR SAfe oPeRATioN. mAKe

suRE THaT THE ouTsIDE VENTs oN THE suPPlY REGulaToRs

AND THe SAfeTY VeNT VALVeS ARe PRoTeCTeD AGAiNST

BLoCKAGe. THeSe ARe PARTS of THe GAS SuPPLY SYSTem, NoT

THe HeATeR. VeNT BLoCKAGe mAY oCCuR DuRiNG iCe SToRmS.

taBle 9 - gas supply pipe lengths (in feet)

maximum eQuiValent pipe length (feet)

natural gas only

Input Rate

(BTu/HR)

Schedule 40 iron Pipe - Nominal Diameter

1/2"

3/4"

1"

1 1/4"

1 1/2"

120,000

20

70

200

200

200

154,000

10

40

150

200

200

180,000

-

30

100

200

200

199,000

-

30

90

200

200

250,000

-

20

60

200

200

275,000

-

10

50

200

200

310,000

-

10

40

150

200

366,000

-

-

30

100

200

390,000

-

-

20

100

200

Natural Gas 0.60 Specific Gravity, 0.50" W.C. Pressure Drop

IT Is IMPoRTaNT To GuaRD aGaINsT Gas ValVE FoulING FRoM

CoNTAmiNANTS iN THe GAS WAYS. SuCH fouLiNG mAY CAuSe

imPRoPeR oPeRATioN, fiRe oR eXPLoSioN.
if CoPPeR SuPPLY LiNeS ARe uSeD THeY muST Be iNTeRNALLY

TiNNeD AND CeRTifieD foR GAS SeRViCe. BefoRe ATTACHiNG

THe GAS LiNe, Be SuRe THAT ALL GAS PiPe iS CLeAN oN THe

iNSiDe.
To TRaP aNY DIRT oR FoREIGN MaTERIal IN THE Gas suPPlY

LiNe, A DiRT LeG (SomeTimeS CALLeD SeDimeNT TRAP oR DRiP

LeG) muST Be iNCoRPoRATeD iN THe PiPiNG (See fiG. 21). THe

DiRT LeG muST Be ReADiLY ACCeSSiBLe AND NoT SuBJeCT

To fReeZiNG CoNDiTioNS. iNSTALL iN ACCoRDANCe WiTH

ReCommeNDATioNS of SeRViNG GAS SuPPLieRS. RefeR To

THE laTEsT VERsIoN oF THE NATioNAL fueL GAS CoDe.
To prevent damage, care must be taken not to apply too much torque

when attaching gas supply pipe to gas valve inlet.
Apply joint compounds (pipe dope) sparingly and only to the male threads

of pipe joints. Do not apply compounds to the first two threads. use com-

pounds resistant to the action of liquefied petroleum gases.
BefoRe PLACiNG THe HeATeR iN oPeRATioN, CHeCK foR GAS

LeAKAGe. use soap and water solution or other material acceptable for

the purpose in locating the leaks. Do NoT uSe mATCHeS, CANDLeS,

fLAme oR oTHeR SouRCeS of iGNiTioN foR THiS PuRPoSe.
DiSCoNNeCT THe HeATeR AND iTS mANuAL GAS SHuToff VALVe

FRoM THE Gas suPPlY PIPING sYsTEM DuRING aNY suPPlY

PReSSuRe TeSTiNG eXCeeDiNG 1/2 PSiG. GAS SuPPLY LiNe

muST Be CAPPeD WHeN DiSCoNNeCTeD fRom THe HeATeR.

foR TeST PReSSuReS of 1/2 PSiG oR LeSS THe APPLiANCe

NeeD NoT Be DiSCoNNeCTeD, BuT muST Be iSoLATeD fRom

THe SuPPLY PReSSuRe TeST BY CLoSiNG THe mANuAL GAS

SHuToff VALVe.

gas piping and dirt leg installation

figure 21.

purging

Gas line purging is required with new piping or systems in which

air has entered.
PuRGING sHoulD BE PERFoRMED BY PERsoNs

eXPeRieNCeD iN THiS TYPe GAS SeRViCe. To AVoiD RiSK

of fiRe oR eXPLoSioN, PuRGe DiSCHARGe muST NoT

eNTeR CoNfiNeD AReAS oR SPACeS WHeRe iGNiTioN CAN

oCCuR. THe AReA muST Be WeLL VeNTiLATeD AND ALL

SouRCeS of iGNiTioN muST Be iNACTiVATeD oR RemoVeD.
gas meter siZe — natural gases only
Be sure the gas meter has sufficient capacity to supply the full

rated gas input of the water heater as well as the requirements of

all other gas fired equipment supplied by the meter. if gas meter

is too small, ask the gas company to install a larger meter having

adequate capacity.

gas pressure regulator

The gas pressure regulator is built into the gas valve and is

equipped to operate on the gas specified on model and rating

plate. The regulator is factory adjusted to deliver gas to burner at

correct water column pressure allowing for a nominal pressure

drop through the controls.
The minimum gas supply pressure for input adjustment must not

be less than 5.2" w.c. (1.12 kPa) for natural gas.
Do not subject the combination gas valve to inlet gas pressures

of more than 14.0” W.C. (3.48 kPa) - natural gas. A supply gas

regulator is necessary if higher gas pressures are encountered. if a

supply gas regulator is installed on the gas supply line, the maximum

recommended pressure for the regulated gas supply is 11" W.C.
Gas pressure specified in Table 10, refer to flow pressure taken

at pressure tap of automatic gas valve while heater is operating.

taBle 10.

manifold gas pressure in inches

of water column (all models*)

type of gas

natural

3.5 (0.87 kPa)