installation diagrams - top inlet/outlet usage

The type, size and location of the relief valves must be in

accordance with local codes. The locations of the relief valves

shown in the installation diagrams are typical. See pages 34-48.

The heater has a factory installed high temperature limit switch

and temperature and pressure relief valve.
Cold water lines to heater should be installed as shown in order

to minimize gravity circulation of hot water to building cold water

lines.
A listed temperature and pressure relief valve of adequate capacity

is installed on the heater. The locations shown in the installation

diagrams on the following pages are typical.
The discharge opening of the temperature and pressure relief

valve, located in front of the heater must be piped to an open drain

and should not be subject to freezing temperatures.
install in accordance with all local codes.
use of the top inlet water connection requires installation of an inlet

dip tube (refer to figure 19). The tube is supplied in the heater.

follow caution labels if applying heat to this fitting. Do not allow

pipe dope to contact the plastic tube during installation.

tuBe inlet installation

figure 19.

code restrictions

use of the top inlet water connection is not permitted on

installations in the state of North Carolina, due to the material

of the tube (Polypropylene). Where such code restrictions

exist, use only lower inlet tank connection. This may also

require a heat trap piping configuration - check local codes.

The “Top outlet” connection may still be used on these

applications. Plug or cap all unused openings in the tank

before filling with water.

temperature setting should not exceed

safe use temperature at fixtures. see water

temperature control and mixing ValVes on

page 11. if higher preheat temperatures are

necessary to oBtain adeQuate Booster output,

add an anti-scald ValVe for hot water supplied

to fixtures.