IDS INDUSTRIAL DISPENSER
INSTRUCTIONS
IN-IDS-08
7
OPEN
1
2
4
12
8
11
10
9
'RED' Jumper
Dispense control
switchboard
Dispense
Switches
640 320 160 80 40 20 10
OFF
SPEED[RPM]
OFF
FL
U
ID METERIN
G
IN
C.
P
C
B 300554
P
/N 200293
2
7 6 5 4 3 2 1
#200293
11 10 9
JP
3
JP1
S
W1
The switches are set up as a binary system. This means that multiple switches will add their values to-
gether. For example, to set the motor to run at 500 rpm you must turn on switch 6, 5 and 2 (320+160+20
= 500 rpm). The switches can give a maximum speed of 1000rpm.
The controller will run at a constant pre-set speed via switches 1 through 7, until control current to P1 Pin
9 (VIOLET). is removed. When the current is removed the unit returns to “one cycle per start signal”. At
the first cycle of the dispense mode the pump will “home” itself to the proper starting point. All following
dispense cycles will then home to the proper start position.
Fig 2B
5.0 Speed switches –Switchboard # 200293
The SPEED switches 1 -7 are used for changing the speed settings.