beautypg.com

Ids industrial dispenser instructions – FMI IDS User Manual

Page 5

background image

IN-IDS-08

5

VOLTS

OPTO-OUTPUT

OHMS

TRANSISTOR OUTPUT

OHMS

RELAY OUTPUT,

OHMS

6

220

220

270

9

390

390

470

12

620

620

680

15

820

820

820

18

1000

1000

1000

24

1300

1300

1500

28

1600

1600

1800

30

2000

2000

2000

NOTE: These are the closest values of current limiting 5%, ¼ watt resistors for the applied voltages. Volt-
age control sources must have series resistors as shown in Table above, to limit control signal currents to
the input opto-isolators, Pins 3, 6, 9, on P1.

2.2 RUN / PURGE MODE
A current of 6 to 20mA must be supplied continuously throughout the signal current input at P1, Pin 9
(VIOLET) to keep the dispenser in a continuous run mode. THE ABSENCE OF THIS SIGNAL WILL
HOLD THE PUMP IN A DISPENSE MODE ONLY
. Run / Purge Actuation is handled by Pin 9 (VIOLET)
(+ side sinking) and 7 (WHITE) (return) on the input connector P1 (see Figure 1, Page 1), by providing a
current of 6 to 20mA through a switch closure, PLC, Relay, Mechanical Timer/Counter or transistor output

2.3 Timed/Count Dispense/Continuous Run Mode
To activate this mode for a timed dispense system, the closing of dispense switch 9 is done externally
using a control signal current input at P1 Pin 9 (VIOLET) for one dispense per signal. The pump will
begin running when this connection is closed, and rotation will cease when the control current is turned
off from Pin 9 of P1. The current must be provided through a resistor (the typical values are shown
on Table 2 below) from a counter or timer that can control a SPST relay or switch closure. External
counters and PLCs can use the VERIFY SIGNAL OUTPUT (P1 Pin 3 (BLUE), verify return common Pin 5
(ORANGE)) to sense and count each revolution pulse. If no PLC is used, a standard industrial counter
such as OMRON H7CR can be set to count up to 9999999 revolutions, and then stop.

Table 2

IDS INDUSTRIAL DISPENSER

INSTRUCTIONS

1