SECTION 10: W

IRING

47 of 71

For 4-20mA control of the heater(s) firing rate, the
following control conditions apply:

ON/OFF relay at the external controller or BMS must
be wired to R and W terminals on the heater control
board to turn the heater ON and OFF.
(Open Circuit = OFF, Closed Circuit = ON).
Minimum rated input at 1% of signal (0-4 mA).
Full rated input at 90% of signal (18 mA).
Input varies linearly between 4 mA and 18 mA.

BMS controllers often offer PID loop control that can
optimize output signal and rate of change of the
output signal. Common analog application is defined
as follows:

1. BMS sensors that monitor zone air

temperatures are located in the heating space.

2. Based on sensed temperatures, the BMS will

output an analog signal for the desired heater(s)
firing rate.

3. As heater(s) receive the analog signal from the

BMS, the heater(s) modulate to the correspond-
ing firing rate.

4. As sensed air temperature rises closer to the

desired temperature setpoint, the BMS will
reduce the output signal, in turn reducing heater
firing rate.

5. Upon satisfying temperature setpoint, the BMS

will either:

a. Turn off the heater.

b. Reduce the signal so that the minimum

heater firing rate is maintained until the
sensed temperature rises above the
setpoint to a cut-off limit temperature when
the BMS turns off the heater.

FIGURE 27: Analog Control Signal Wiring Diagram

*OPTIONAL

SWITCH

SATELLITE HEATER CONTROL

FOR SATELITTE
CONTROLLERS, J9 JUMPER CAN BE
LEFT IN ORIGINAL POSITION
REGARDLESS OF CONTROL METHOD.

J10 JUMPER POSITION
SHOWS "SATELLITE" DESIGNATION.

MODULATION CONTROL WIRING
TO ADDITIONAL SATELLITE
HEATER CONTROL TERMINALS
T28 and T29.

ON/OFF SWITCH
REQUIRED

MODULATION CONTROL WIRING
TO SATELLITE HEATERS

CENTRAL HEATER CONTROL

REMOTE ANALOG
CONTROL
SIGNAL FROM SEPARATE
CONTROLLER
0-10Vdc OR 4-20mA

ANALOG INPUT CONTROL IS
USED TO SELECT ANALOG
SIGNAL TYPE 0-10Vdc OR 4-20mA
(4-20mA POSITION SHOWN).

J10 JUMPER POSITION
SHOWS "CENTRAL"
DESIGNATION AND
"ANALOG" CONTROL METHOD.

J10

J9

W

R

-

+

-

+

-

+

OUT

RA
TE

FIRI

N

G

IN

RA
TE

FIRI

N

G

EXT

. PO

T

G

N

D

W
IPER

HIGH

G

N

D

BA
R

SLIDE

G

N

D

THERMIS

T

OR

IN

PUT

A

N

AL
OG

THERMOSTAT

T31

T29

T19

T18

T16

T14

T27

T25

T30

T28

T17

T15

T13

T26

T24

-

+

J10

J9

W

R

-

+

-

+

-

+

OUT

RA
TE

FIRI

N

G

IN

RA
TE

FIRI

N

G

EXT

. PO

T

G

N

D

W
IPER

HIGH

G

N

D

BA
R

SLIDE

G

N

D

THERMIS

T

O

R

IN

PUT

A

N

AL
OG

THERMOSTAT

T31

T29

T19

T18

T16

T14

T27

T25

T30

T28

T17

T15

T13

T26

T24

A B

A B

* Separate on/off switch is optional for "satellite" heaters (install at user level). On/Off switch is used to
disable heater operation or reset a heater that is in "lockout" mode. If on/off switch is not desired, leave
jumper wire between R and W terminals in place.