beautypg.com

Section 10: wiring, 1 standard heater configuration, Figure 22: zone sensor wiring diagram – RG CTH3-150 User Manual

Page 45: Danger

background image

SECTION 10: W

IRING

39 of 71

SECTION 10: WIRING

Heater must be grounded in accordance with
applicable codes: United States: refer to National

Electrical Code

®

NFPA 70 - latest revision

Canada: refer to Canadian Electrical Code, CSA
C22.1 Part I - latest revision.

If any of the original internal wiring must be replaced,
it must be replaced with wiring materials having a
temperature rating of at least 105°C and 600 Volts.

10.1 Standard Heater Configuration

From the factory, the heater is configured for zone
sensor control. Connect zone sensor to the heater
control as shown

on Page 39, Figure 22.

If additional heaters are in the same heating zone,
control wiring must be installed between the heaters’
controls as shown

on Page 39, Figure 22.

For additional details or for use with heat demand
control devices other than the zone sensor,

see Page

40, Section 10.2 through Page 48, Section 10.4.9.

FIGURE 22: Zone Sensor Wiring Diagram

DANGER

Electrical Shock Hazard

Disconnect electric before service.

Heater must be properly grounded.

Failure to follow these instructions can result
in death or electrical shock.

MODULATION CONTROL WIRING
TO SATELLITE HEATERS

CENTRAL HEATER CONTROL

OFF

ON

-LCD+

+FAN-

SEN

ZONE SENSOR

SET

J10

W

R

-

+

-

+

-

+

OUT RA

TE

FIRING

IN

RA
TE

FIRING

EXT
. POT

GND

WIPER

HIGH

GND

BAR SLIDE

GND

THERMISTOR

INPUT ANALOG

THERMOSTAT

T31

T29

T19

T18

T16

T14

T27

T25

T30

T28

T17

T15

T13

T26

T24

MODULATION CONTROL WIRING
TO ADDITIONAL SATELLITE
HEATERS CONTROL TERMINALS
T28 and T29.

*OPTIONAL

SWITCH

SATELLITE HEATER CONTROL

J10

W

R

-

+

-

+

-

+

OUT RA

TE

FIRING

IN

RA
TE

FIRING

EXT
. POT

GND

WIPER

HIGH

GND

BAR SLIDE

GND

THERMISTOR

INPUT ANALOG

THERMOSTAT

T31

T29

T19

T18

T16

T14

T27

T25

T30

T28

T17

T15

T13

T26

T24

A B

A B

* Separate on/off switch is optional for
"satellite" heaters (install at user level). On/
Off switch is used to disable heater operation
or reset a heater that is in "lockout" mode. If
on/off switch is not desired, leave jumper wire
between R and W terminals in place.

Description

Part Number

Zone Sensor, 40° - 75°

10081530