Malfunction

Possible cause

Measure

No output signal /

no switch signal

Failure of power supply

or wiring interrupted

Check power supply and

wiring; replace defective

components

Electronic defect

through incorrect

supply voltage or

external voltage

Return instrument to

manufacturer for repair

Steady signal despite

pressure changes

Pressure entry blocked Check tailpipes and

pressure entry bore, if ne-

cessary clean it carefully

Excessively high,

steady signal despite

pressure changes

Electronic defect

through incorrect

supply voltage or

external voltage

Return instrument to

manufacturer for repair

Full span reading

too low

Supply voltage too low

Adjust supply voltage

Load impedance

too high

Consider max. permissible

load

Zero point shifted

Return instrument to

manufacturer for repair

Zero signal too low /

too high

Zero point shifted

Return instrument to

manufacturer for repair

Switch signal instable Supply voltage too low

Adjust supply voltage

10. Technical data

For technical data please refer to the technical data sheets.
PV 11.01 intelliGAUGE, model PGT01, plug connector, NS 40

PV 11.02 intelliGAUGE, model PGT02, cable outlet, NS 40

PV 11.05 intelliGAUGE, model PGT10, plastic case, IP 41, NS 40, 50

PV 11.06 intelliGAUGE, model PGT11, stainless steel case, IP 41, NS 40, 50

PV 11.03 intelliGAUGE, model PGT21, stainless steel case, NS 50

PV 21.03 switchGAUGE, model PGS05, cable outlet, NS 40

PV 21.05 switchGAUGE, model PGS06, plastic case, IP 41, NS 40, 50

PV 21.06 switchGAUGE, model PGS07, stainless steel case, IP 41, NS 40, 50

PV 21.04 switchGAUGE, model PGS25, stainless steel case, NS 50

10

GB

9. Trouble shooting / 10. Technical data

9. Trouble shooting

This manual is related to the following products: