WIKA operating instructions DELTA-plus, DELTA-comb and DELTA-switch

18

14093265.01 03/2014 GB/D/F/E

6. Commissioning, operation

Safety instructions for installation

Follow the installation and safety instructions within the

operating instructions.

Install instruments in accordance with the manufacturer's

instructions and the valid standards and regulations.

The instruments do not provide for incorporated overcurrent protectors!

In order to prevent the contacts from welding through overload, suitable

protection systems must be implemented by the operator!

Only connect circuits with the same voltage and type of protection to the

switch contacts and connecting cables.

Limit the maximum current, using external measures, to a value of ≤ 5 A per

circuit.

Size the connecting cables for the largest current strength in the circuits.

Precise wiring schemes can be seen in the following connection diagram. In

addition both the pin assignment and the required power supply are stated on the

product label of the case circumference.

Electrical connection via:

Cable gland and cable

1st

contact

2nd contact

Cable socket or angular connector

per DIN 43651

2nd contact

1st contact

Cable terminal box

Information

For the safety circuit, which will switch off the heating if the

steam generator falls below the minimum flow, only the normally

open contact of the changeover switch should be connected (i.e.

with Δp = 0 open circuit)!