28
WIKA operating instructions pressure switch model PSD-3x
GB
11430486.06 02/2012 GB/D/F/E
6. Commissioning, operation
Index
(decimal)
Object
name
Format
Access Value range
Factory
setting
Remarks
76
DR1
16 Bit unsigned R/W
0 … 50,000 (0 ... 50 s)
0
Switch delay time reset
point 1
77
DS2
16 Bit unsigned R/W
0 … 50,000 (0 ... 50 s)
0
Switch delay time switch
point 2
78
DR2
16 Bit unsigned R/W
0 … 50,000 (0 ... 50 s)
0
Switch delay time reset
point 2
240
MBA
32 Bit IEEE 754
Float
R
-
1,000
The pressure value is
always linearised such that
the MBA equals the value
1000 and the MBE equals
the value 9000.
241
MBE
32 Bit IEEE 754
Float
R
-
9,000
The pressure value is
always linearised such that
the MBA equals the value
1,000 and the MBE equals
the value 9,000.
250
DISR
8 Bit
Enumeration
R/W
0 = Standard
1 = 180° rotated
0
Turn display indicator by
180°
251
DISM
8 Bit
Enumeration
R/W
0 = Act
1 = HIGH
2 = LOW
3 = SP1/FH1
4 = RP1/FL1
5 = SP2/FH2
6 = RP2/FL2
7 = Off
0
Display value in display
mode
252
PAS
16 Bit unsigned R/W
0 … 9,999
-
Enter password in order to
set the parameters at the
instrument. Password 0 =
no password
253
LOCK
8 Bit
Enumeration
R/W
0 = Unlocked
1 = Locked
0
General keylock