Commissioning, operation – WIKA PSD-31 User Manual

Page 18

background image

18

WIKA operating instructions pressure switch model PSD-3x

GB

11430486.06 02/2012 GB/D/F/E

6. Commissioning, operation

Connection diagrams

Zero point adjustment

Check the indicated zero point on the display during commissioning.

Should an offset be displayed as a result of installation, this can be reset in programming mode with the

0SET parameter

Carry out zero point adjustment for relative and vacuum pressure measuring ranges in a

depressurised state.

Carry out zero point adjustment of absolute pressure ranges from 0 bar absolute

(vacuum). Since appropriate references are required for this, we recommend that this is

only carried out by the manufacturer.

6.2 Making the electrical connection

The instrument must be earthed via the process connection!

The power supply for the pressure switch must be made via an energy-limited electrical circuit in

accordance with section 9.3 of UL/EN/IEC 61010-1 or an LPS to UL/EN/IEC 60950-1 or class 2 in

accordance with UL1310/UL1585 (NEC or CEC). The power supply must be suitable for operation

above 2,000 m should the pressure switch be used at this altitude.

For cable outlets, make sure that no moisture enters at the cable end.

Circular connector M12 x 1; 4-pin

Assignment

U

+

U-

S

+

SP1

SP2

1

3

2

4

2

Circular connector M12 x 1; 5-pin

Assignment

U

+

U-

S

+

SP1

SP2

1

3

5

4

2