6. Commissioning, operation

6.6 Description of the IO-Link functionality (optional)

IO-Link is a point-to-point connection for the communication of the PSD-3x with an IO-Link master.
Physical layer

The PSD-3x supports the following features:

IO-Link specification: Version 1.0

SIO mode:

Yes

Minimum cycle time: 2.3 ms

Rate:

COM2 (38.4 kBaud)

Process data length: 16 bit (Frametype 2.2)

Process data

The PSD-3x has 1 or 2 digital outputs. Both switching outputs are transmitted as process data over the

IO-Link.

In the 'SIO Mode' (Standard I/O Mode), i.e. no IO-Link operation, the switching output 1 will switch on

pin 4 of the M12 connector.

In the IO-Link communication mode, this pin is reserved exclusively for communication. Switching

output 2 is always switched in addition on pin 2 of the M12 connector.

With a Frametype 2.2, the 16-bit process data from the pressure switch are transmitted cyclically. Bit

0 is the state of switching output 1 and Bit 1 is the state of switching output 2. Where 1 and DC 24 V

correspond to the "closed" logic state of the respective output.

The remaining 14 bits contain the analogue value measured by the pressure switch. The start of the

measuring range (MBA) corresponds to a value of 1,000 d and the end of the measuring range (MBE)

corresponds to a value of 9,000 d.

Bit

Process value

Value range

0

OU1

0 = off, 1 = on

1

OU2

0 = off, 1 = on

2 … 15

Measured value (integer)

1,000 d = MBA

9,000 d = MBE